product brand nameSIPLUS
transfer rate
at the 1st interface / according to PROFIBUS9.6 kbit/s ... 12 Mbit/s
interfaces
number of interfaces / according to Industrial Ethernet0
at the 1st interface / according to PROFIBUS1
for power supply1
at the 1st interface / according to PROFIBUS9-pin Sub-D socket (RS485)
for power supply3-pole terminal block
supply voltage, current consumption, power loss
type of voltage / of the supply voltageDC
supply voltage / external24 V
supply voltage / external / at DC / rated value24 V
relative positive tolerance / at DC / at 24 V20 %
relative negative tolerance / at DC / at 24 V20 %
from external supply voltage / at DC / at 24 V / typical0.1 A
power loss [W]2.4 W
ambient conditions
during operation-25 ... +55 °C
during storage-40 ... +70 °C
during transport-40 ... +70 °C
note+70 °C for 10 min (OT1, ST1/ST2 according to EN 50155)
installation altitude / at height above sea level / maximum2000 m
ambient condition / relating to ambient temperature - air pressure - installation altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
with condensation / according to IEC 60068-2-38 / maximum100 %; RH including condensation/frost (no commissioning when condensation is present), horizontal installation
chemical resistance / to commercially available cooling lubricantsYes; incl. airborne diesel and oil droplets
conformity according to EN 60721-3-3Yes; Class 3B2 mold and fungal spores (excluding fauna), Class 3B3 on request
conformity according to EN 60721-3-5Yes; Class 5B2 mold and fungal spores (excluding fauna), Class 5B3 on request
conformity according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray in accordance with EN 60068-2-52 (Severity 3). The supplied plug covers must remain in place on the unused interfaces during operation.
conformity according to EN 60721-3-5Yes; Class 5C3 (RH < 75%) including salt spray acc. to EN 60068-2-52 (Severity level 3). The supplied plug covers must remain in place over the unused interfaces during operation!
conformity according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation.
conformity according to EN 60721-3-5Yes; Class 5S3 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation!
coating / for equipped printed circuit board / according to EN 61086Yes; Class 2 for high availability
type of coating / protection against pollution according to EN 60664-3Yes; Protection of the type 1
type of coating / for electronic devices in railway applications according to EN 50155Yes; Protective coating of the Class PC2 according to EN 50155:2018
type of test / of the coating / according to MIL-I-46058CYes; Coating discoloration during service life possible
product conformity / of the coating / Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, class A
protection class IPIP20
design, dimensions and weights
module formatCompact module S7-1200 single width
width30 mm
height100 mm
depth75 mm
net weight0.134 kg
35 mm top hat DIN rail mountingYes
S7-300 rail mountingNo
wall mountingYes
product features, product functions, product components / general
per CPU / maximum3
performance data / PROFIBUS DP
DPV1Yes
on DP master / operable32
of the address range of the inputs / as DP master / total512 byte
of the address range of the outputs / as DP master / total512 byte
of the address range of the inputs / per DP device244 byte
of the address range of the outputs / per DP device244 byte
of the address range of the diagnostic data / per DP device240 byte
DPV0No
DPV1No
performance data / S7 communication
maximum8; max. 4 connections to other S7 stations
with PG connections / maximum1
with PG/OP connections / maximum3
performance data / multi-protocol mode
without DP / maximum8
with DP / maximum8
performance data / telecontrol
TCP/IPNo
product functions / management, configuration, engineering
requiredSTEP 7 Basic/Professional
product function / is supported / identification linkYes; acc. to IEC 61406-1:2022
product functions / position detection
certificate of suitability / railway application in accordance with EN 50121-3-2Yes; EMC for railway vehicles
certificate of suitability / railway application in accordance with EN 50121-4Yes; EMC for signaling and telecommunications equipment
certificate of suitability / railway application in accordance with EN 50124-1Yes; Railway applications - Overvoltage category OV2 pollution degree PD2 rated impulse voltage UNi = 0.5 kVUNm = DC 24
certificate of suitability / railway application in accordance with EN 50125-1Yes; Railway vehicles - See ambient conditions
certificate of suitability / railway application in accordance with EN 50125-2Yes; Fixed-electrical installations - see ambient conditions
certificate of suitability / railway application in accordance with EN 50125-3Yes; Signal and telecommunications equipment - see Ambient conditions vibrations and shocks: Application point outside the rails (distance 1 m to 3 m from rail)
certificate of suitability / railway application in accordance with EN 50155Yes; Railway vehicles - temperature class OT1, ST1/ST2, horizontal mounting position
certificate of suitability / railway application in accordance with EN 61373Yes; Railway vehicles - Vibrations and shocks Category 1 Class A/B
certificate of suitability / fire protection in accordance with EN 45545-2Yes; Railway vehicles - for proof, see Service & Support