product brand nameSIPLUS
transfer rate
at the 1st interface10 ... 100 Mbit/s
interfaces
number of interfaces / according to Industrial Ethernet1
at the 1st interface / according to Industrial Ethernet1
for power supply0
at the 1st interface / according to Industrial EthernetRJ45 port
supply voltage, current consumption, power loss
type of voltage / of the supply voltageDC
supply voltage / 1 / from backplane bus5 V
from backplane bus / at DC / at 5 V / typical0.25 A
power loss [W]1.25 W
ambient conditions
for vertical installation / during operation-25 ... +60 °C
for horizontally arranged busbars / during operation-25 ... +70 °C
during storage-40 ... +70 °C
during transport-40 ... +70 °C
note+70 °C for 10 min (OT1, ST1/ST2 according to EN 50155)
installation altitude / at height above sea level / maximum2000 m
ambient condition / relating to ambient temperature - air pressure - installation altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
with condensation / according to IEC 60068-2-38 / maximum100 %; RH including condensation/frost (no commissioning when condensation is present), horizontal installation
chemical resistance / to commercially available cooling lubricantsYes; incl. airborne diesel and oil droplets
conformity according to EN 60721-3-3Yes; Class 3B2 mold and fungal spores (excluding fauna), Class 3B3 on request
conformity according to EN 60721-3-5Yes; Class 5B2 mold and fungal spores (excluding fauna), Class 5B3 on request
conformity according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray in accordance with EN 60068-2-52 (Severity 3). The supplied plug covers must remain in place on the unused interfaces during operation.
conformity according to EN 60721-3-5Yes; Class 5C3 (RH < 75%) including salt spray acc. to EN 60068-2-52 (Severity level 3). The supplied plug covers must remain in place over the unused interfaces during operation!
conformity according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation.
conformity according to EN 60721-3-5Yes; Class 5S3 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation!
coating / for equipped printed circuit board / according to EN 61086Yes; Class 2 for high availability
type of coating / protection against pollution according to EN 60664-3Yes; Protection of the type 1
type of coating / for electronic devices in railway applications according to EN 50155Yes; Protective coating of the Class PC2 according to EN 50155:2017
type of test / of the coating / according to MIL-I-46058CYes; Coating discoloration during service life possible
product conformity / of the coating / Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, class A
protection class IPIP20
design, dimensions and weights
module formatCompact module S7-1200 single width
width30 mm
height110 mm
depth75 mm
net weight0.122 kg
35 mm DIN-rail mountingYes
wall mountingYes
product features, product functions, product components / general
per CPU / maximum3
product functions / cloud connectivity
Message Queuing Telemetry Transport (MQTT)Yes
Advanced Message Queuing Protocol (AMQP)No
trigger managementYes
time stampingYes
product feature / for cloud connectivity / buffered message frame memoryNo
number of active connections / for cloud connectivity1
number of data points per device / maximum500
performance data / open communication
by means of T blocks / maximumlike CPU
performance data / S7 communication
maximumlike CPU
performance data / IT functions
as email client / maximum1
performance data / telecontrol
node stationNo
substationYes
TIM control centerNo
control center connectionFor use with TeleControl Server Basic, WinCC and PCS7
by means of a permanent connectionsupported
noteConnection to SCADA system via Telecontrol Server Basic and Standard Telecontrol protocols
DNP3Yes
IEC 60870-5Yes
product function / data buffering if connection is abortedYes; 64,000 events
number of data points per device / maximum200
in send direction / maximum3
in receive direction / maximum15
performance data / teleservice
diagnostics function / online diagnostics with SIMATIC STEP 7Yes
program download with SIMATIC STEP 7Yes
remote firmware updateYes
product functions / management, configuration, engineering
requiredSTEP 7 Basic/Professional
product function / is supported / identification linkYes; acc. to IEC 61406-1:2022
product functions / diagnostics
product function / web-based diagnosticsYes
product functions / security
firewall versionstateful inspection
product function / with VPN connectionIPsec, SINEMA RC
type of encryption algorithms / with VPN connectionAES-256, AES-192, AES-128, 3DES-168
type of authentication procedure / with VPN connectionPreshared key (PSK), X.509v3 certificates
type of hashing algorithms / with VPN connectionMD5, SHA-1, SHA-2
number of possible connections / with VPN connection8
password protection for Web applicationsNo
password protection for teleservice accessNo
encrypted data transmissionYes
ACL - IP-basedNo
ACL - IP-based for PLC/routingNo
switch-off of non-required servicesYes
blocking of communication via physical portsNo
log file for unauthorized accessNo
product functions / time
NTPYes
NTP (secure)Yes
from NTP-serverYes
from control centerYes
product functions / position detection
certificate of suitability / railway application in accordance with EN 50121-3-2Yes; EMC for railway vehicles
certificate of suitability / railway application in accordance with EN 50121-4Yes; EMC for signaling and telecommunications equipment
certificate of suitability / railway application in accordance with EN 50124-1Yes; Railway applications - Overvoltage category OV2 pollution degree PD2 rated impulse voltage UNi = 0.5 kVUNm = DC 24
certificate of suitability / railway application in accordance with EN 50125-1Yes; Railway vehicles - See ambient conditions
certificate of suitability / railway application in accordance with EN 50125-2Yes; Fixed-electrical installations - see ambient conditions
certificate of suitability / railway application in accordance with EN 50125-3Yes; Signal and telecommunications equipment - see Ambient conditions vibrations and shocks: Application point outside the rails (distance 1 m to 3 m from rail)
certificate of suitability / railway application in accordance with EN 50155Yes; Railway vehicles - temperature class OT1, ST1/ST2, horizontal mounting position
certificate of suitability / railway application in accordance with EN 61373Yes; Railway vehicles - Vibrations and shocks Category 1 Class A/B
certificate of suitability / fire protection in accordance with EN 45545-2Yes; Railway vehicles - for proof, see Service & Support