General information
Product type designationPN/PN coupler
FW update possibleYes
based on6ES7158-3AD10-0XA0
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo; For operation on isochronous bus
Tool changerYes; Docking station and docking unit
Local coupling, IO dataYes
— Number of coupling modules16
— Number of coupling submodules per module4; 1x write, 3x read
Local coupling, data recordsYes
— Number of coupling modules16
— Number of coupling submodules per module4; 1x write, 3x read
— Record length, max.4 096 byte
— FIFO depth in storage mode8
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
PROFINET from GSD version/GSD revisionGSDML V2.4.x
Installation type/mounting
MountingMounting rail 7.5 mm and 15 mm
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Mains buffering
Mains/voltage failure stored energy time10 ms
Input current
Current consumption, max.360 mA; For 19.2 V input voltage at the right-hand supply terminal, including 2 plugged BA 2x LC
Inrush current, max.1.6 A
I²t0.031 A²·s
from supply voltage 1L+, max.320 mA; For 19.2 V input voltage at the left-hand supply terminal, including 2 plugged BA 2x LC
Power loss
Power loss, typ.4 W; For 24 V input voltage and 2 plugged BA 2x RJ45 If BusAdapters with an optical interface are plugged, there is an additional 750 mW per optical interface (3 W with 2 plugged BA 2x LC)
Address space per module
Address space per module, max.254 byte; max. 254 bytes of input data and 253 bytes of output data
Address space per station
Address space per station, max.1 440 byte; per input / output
Submodules
Number of submodules per station, max.116
Interfaces
Number of PROFINET interfaces2; One PROFINET interface per line side
Optical interfaceYes; Via SIMATIC BusAdapter
Transmission rate, max.100 Mbit/s
Interface types
Number of ports2; via BusAdapter
integrated switchYes
BusAdapter (PROFINET)Yes; Compatible BusAdapter: BA 2x RJ45, BA 2x FC, BA 2x SCRJ, BA SCRJ / RJ45, BA SCRJ / FC, BA 2x LC, BA LC / RJ45, BA LC / FC
Protocols
PROFINET IO DeviceYes
Open IE communicationYes
Media redundancyYes; As MRP or MRPD client; max. 50 or 30 devices in the ring
Services
— IRTYes
— Dynamic Frame Packing (DFP)Yes
— PROFIenergyNo
— Prioritized startupYes
— Shared deviceYes
— Number of IO Controllers with shared device, max.4; per line side
Interface types
Number of ports2; via BusAdapter
integrated switchYes
BusAdapter (PROFINET)Yes; Compatible BusAdapter: BA 2x RJ45, BA 2x FC, BA 2x SCRJ, BA SCRJ / RJ45, BA SCRJ / FC, BA 2x LC, BA LC / RJ45, BA LC / FC
Protocols
PROFINET IO DeviceYes
Open IE communicationYes
Media redundancyYes; As MRP or MRPD client; max. 50 or 30 devices in the ring
Services
— IRTYes
— Dynamic Frame Packing (DFP)Yes
— PROFIenergyNo
— Prioritized startupYes
— Shared deviceYes
— Number of IO Controllers with shared device, max.4; per line side
RJ 45 (Ethernet)
Transmission procedurePROFINET with 100 Mbit/s full duplex (100BASE-TX)
10 MbpsNo
100 MbpsYes; PROFINET with 100 Mbit/s full duplex (100BASE-TX)
AutonegotiationYes
AutocrossingYes
Protocols
Supports protocol for PROFINET IOYes
EtherNet/IPNo
Protocols (Ethernet)
TCP/IPYes
SNMPYes
LLDPYes
pingYes
ARPYes
Redundancy mode
PROFINET system redundancy (S2)Yes; NAP S2 acc. to IEC
PROFINET system redundancy (R1)No
H-Sync forwardingYes
Media redundancy
— MRPYes
— MRPDYes
Open IE communication
TCP/IPYes
SNMPYes
LLDPYes
Interrupts/diagnostics/status information
Status indicatorYes
AlarmsYes
Diagnostics functionYes; Parameterizable
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
MAINT LEDYes; Yellow LED
LINK LEDYes; 2x green link LEDs on BusAdapter
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Potential separation
between supply voltage and electronicsYes; to power input 2
between Ethernet and electronicsYes
Isolation
Isolation tested with750 V DC (type test) and according to EN 50155 (routine test)
Standards, approvals, certificates
Network loading class3
Railway application
EN 50121-3-2Yes; EMC for rail vehicles
EN 50121-4Yes; EMC for signal and telecommunications systems
EN 50124-1Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC
EN 50125-1Yes; Rail vehicles - see ambient conditions
EN 50125-2Yes; Stationary electrical equipment - see ambient conditions
EN 50125-3Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)
EN 50155Yes; Rail vehicles - temperature class OT4, ST1/ST2, horizontal mounting position
EN 61373Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B
Fire protection acc. to EN 45545-2Yes; For proof of conformity, see Service & Support
Security
PROFINET Security Class1
Ambient temperature during operation
min.-40 °C; = Tmin (incl. condensation/frost)
max.70 °C; = Tmax; +85 °C for 10 min (OT4, ST1/ST2 acc. to EN 50155)
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according to EN 60721-3-5Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request
— to chemically active substances according to EN 60721-3-5Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-5Yes; Class 5S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-5Yes; Class 5M2 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
— against mechanical environmental conditions in agriculture acc. to ISO 15003Yes; level 1 (Location LE) using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Electronic equipment on rolling stock acc. to EN 50155Yes; Class PC2 protective coating acc. to EN 50155:2017
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Mechanics/material
Strain reliefYes; Optional, for RJ45 and FC BusAdapter only
Dimensions
Width100 mm; Minimized with good handling
Height117 mm
Depth74 mm; with mounting rail
Weights
Weight, approx.200 g; without BusAdapter
Other
Note:for use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A, Online Support article 109736776