General information
Product type designationIM 155-6 MF HF
Firmware versionV6.4.1
FW update possibleYes
Vendor identification (VendorID)002AH
Device identifier (DeviceID)0313H
Manufacturer ID according to ODVA (VendorID)0x04E3
Device ID according to ODVA (Product code)0FA2H
based on6ES7155-6MU01-0CN0
Product function
I&M dataYes; I&M0 to I&M4
Module swapping during operation (hot swapping)Yes; Multi-hot swapping
Isochronous modeYes
IRTYes
Tool changerYes; Docking station and docking unit
Local coupling, IO dataYes
— Number of coupling modules6; 1x output + max. 5x input
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
PROFINET from GSD version/GSD revisionGSDML V2.45
Configuration control
via datasetYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Short-circuit protectionYes
Mains buffering
Mains/voltage failure stored energy time10 ms
Input current
Current consumption (rated value)550 mA
Current consumption, max.650 mA
Inrush current, max.1 A
I²t0.05 A²·s
Power loss
Power loss, typ.2 W
Address space per module
Address space per module, max.288 byte; For input and output data respectively
Address space per station
Address space per station, max.1 440 byte
Rack
Quantity of operable ET 200SP modules, max.64; > 60 °C ambient temperature: 48 modules
Submodules
Number of submodules per station, max.256
Interfaces
Transmission procedure100BASE-TX
Number of PROFINET interfaces1; 2 ports (switch)
Interface types
RJ 45 (Ethernet)Yes; with BusAdapter
Number of ports2; with BusAdapter
integrated switchYes
BusAdapter (PROFINET)Yes
Protocols
PROFINET IO DeviceYes
Open IE communicationYes
Media redundancyYes; PROFINET MRP client
Services
— IRTYes; 250 µs to 4 ms in 125 µs frame
— Dynamic Frame Packing (DFP)Yes
— PROFIenergyYes
— Prioritized startupYes
— Shared deviceYes
— Number of IO Controllers with shared device, max.14; 2x PN controller + 2x EtherNet/IP scanner + 10x Modbus TCP master
RJ 45 (Ethernet)
Transmission procedurePROFINET with 100 Mbit/s full duplex (100BASE-TX)
100 MbpsYes
AutonegotiationYes
AutocrossingYes
Protocols
Supports protocol for PROFINET IOYes
PROFIsafeYes
PROFIBUSNo
EtherNet/IPYes
Modbus TCPYes
Number of connections
Number of MtM communication relationships/connections, max.16
Redundancy mode
PROFINET system redundancy (S2)Yes; NAP S2
PROFINET system redundancy (R1)No
H-Sync forwardingYes
Media redundancy
— MRPYes
— MRPDYes
Services
— CIP Implicit MessagingYes
— CIP Explicit MessagingYes
— CIP SafetyNo
— Configuration control via Explicit MessagingNo
— Shared deviceYes; 2x PN controller + 2x EtherNet/IP scanner + 10x Modbus TCP master
— Number of scanners with shared device, max.2
Updating times
— Requested Packet Interval (RPI)2 ms
Address area
— Address space per module, max.288 byte; (246 byte outputs / 288 byte inputs)
— ForwardOpen (Class1 & 32 bit Header)500 byte; (246 byte outputs / 500 byte inputs)
— LargeForwardOpen (Class3)4 002 byte
Connections
— Number of rack connections2
Services
— read coils (code=1)Yes
— read discrete inputs (code=2)Yes
— Read Holding Registers (Code=3)Yes
— write single coil (code=5)Yes
— write multiple coils (code=15)Yes
— Write Multiple Registers (Code=16)Yes
— Parameter change by masterYes
— Modbus TCP Security ProtocolNo
Address space per station
— Address space per station, max.500 byte; (246 byte outputs / 500 byte inputs)
— Access-consistent address space250 byte; (246 byte outputs / 250 byte inputs)
Updating time
— I/O request interval2 ms
Connections
— number of connections per device9; (1x inputs / 2x outputs / 4x volatile registers / 2x Device Info)
Open IE communication
TCP/IPYes
UDPYes
SNMPYes
LLDPYes
ARPYes
IGMPYes
MulticastYes
BroadcastYes
IPv4Yes
IPv6No
Isochronous mode
EquidistanceYes
shortest clock pulse250 µs
max. cycle4 ms
Bus cycle time (TDP), min.250 µs
Jitter, max.1 µs
Interrupts/diagnostics/status information
Status indicatorYes
AlarmsYes
Diagnostics functionYes
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
MAINT LEDYes; Yellow LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
NS LEDYes; green/red LED
MS LEDYes; green/red LED
IO LEDYes; red-green-yellow LED
Connection display LINK TX/RXYes; 2x green link LEDs on BusAdapter
Potential separation
between backplane bus and electronicsNo
between PROFINET and all other circuitsYes; 1500 V AC (type test)
between supply and all other circuitsNo
Permissible potential difference
between different circuitsSafety extra low voltage SELV
Isolation
Isolation tested with750 V DC (type test) and according to EN 50155 (routine test)
Standards, approvals, certificates
Network loading class3
Railway application
EN 50121-3-2Yes; EMC for rail vehicles
EN 50121-4Yes; EMC for signal and telecommunications systems
EN 50121-5Yes; EMC for fixed installations and railway power supply equipment
EN 50124-1Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC
EN 50125-1Yes; Rail vehicles - see ambient conditions
EN 50125-2Yes; Stationary electrical equipment - see ambient conditions
EN 50125-3Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)
EN 50155Yes; Rail vehicles - temperature class OT4, ST1/ST2, horizontal mounting position
EN 61373Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B
Fire protection acc. to EN 45545-2Yes; For proof of conformity, see Service & Support
Security
PROFINET Security Class1
signed firmware updateYes
Secure BootNo
securely removing dataYes
data integrityYes
Ambient temperature during operation
horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.70 °C; = Tmax; +85 °C for 10 min (OT4, ST1/ST2 acc. to EN 50155)
vertical installation, min.-40 °C; = Tmin
vertical installation, max.50 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0//6AG1193-6AB00-0AA0)
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according to EN 60721-3-5Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request
— to chemically active substances according to EN 60721-3-5Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-5Yes; Class 5S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-5Yes; Class 5M2 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0/6AG1193-6AB00-0AA0)
— against mechanical environmental conditions in agriculture acc. to ISO 15003Yes; Level 1 (Location LE) using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0/6AG1193-6AB00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Electronic equipment on rolling stock acc. to EN 50155Yes; class PC2 protective coating acc. to EN 50155
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
ET-Connection
via BU/BA SendYes; + 16 ET 200AL modules
Mechanics/material
Strain reliefYes; Optional
Dimensions
Width50 mm
Height117 mm
Depth74 mm
Weights
Weight, approx.125 g; without BusAdapter
Other
Note:for use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A, Online Support article 109736776