General information
Product type designationIM 155-6 PN ST incl. BA 2x RJ45 and server module
FW update possibleYes
Vendor identification (VendorID)002AH
Device identifier (DeviceID)0313H
Manufacturer ID according to ODVA (VendorID)04E3H
Device ID according to ODVA (Product code)0FA2H
based on6ES7155-6AA02-0BN0
Product function
I&M dataYes; I&M0 to I&M4
Module swapping during operation (hot swapping)Yes; Multi-hot swapping
Isochronous modeNo
IRTYes
— Number of coupling modules6; 1x output + max. 5x input
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Configuration control
via datasetYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Short-circuit protectionYes
Mains buffering
Mains/voltage failure stored energy time10 ms
Input current
Current consumption (rated value)350 mA
Current consumption, max.450 mA
Inrush current, max.1 A
I²t0.05 A²·s
Power loss
Power loss, typ.1.8 W
Address space per module
Address space per module, max.288 byte; For input and output data respectively
Address space per station
Address space per station, max.1 440 byte
Rack
Quantity of operable ET 200SP modules, max.32
Quantity of operable ET 200AL modules, max.16
Submodules
Number of submodules per station, max.256
Interfaces
Number of PROFINET interfaces1; 2 ports (switch)
Interface types
RJ 45 (Ethernet)Yes; with BusAdapter
Number of ports2; with BusAdapter
integrated switchYes
BusAdapter (PROFINET)Yes
Protocols
PROFINET IO DeviceYes
Open IE communicationYes
Media redundancyYes; PROFINET MRP client
Services
— IRTYes; 1 ms to 4 ms at an interval of 125 µs
— Dynamic Frame Packing (DFP)Yes
— Fast ForwardingYes
— FragmentationYes
— PROFIenergyYes
— Prioritized startupYes
— Shared deviceYes
— Number of IO Controllers with shared device, max.4
RJ 45 (Ethernet)
Transmission procedurePROFINET with 100 Mbit/s full duplex (100BASE-TX)
100 MbpsYes
AutonegotiationYes
AutocrossingYes
Protocols
Supports protocol for PROFINET IOYes
PROFIsafeYes
PROFIBUSNo
EtherNet/IPNo
Modbus TCPNo
Redundancy mode
PROFINET system redundancy (S2)No
Media redundancy
— MRPYes
— MRPDNo
Open IE communication
TCP/IPYes
UDPYes
SNMPYes
LLDPYes
ARPYes
IGMPYes
MulticastYes
BroadcastYes
IPv4Yes
IPv6No
Interrupts/diagnostics/status information
Status indicatorYes
AlarmsYes
Diagnostics functionYes
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
MAINT LEDYes; Yellow LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Connection display LINK TX/RXYes; 2x green link LEDs on BusAdapter
Potential separation
between backplane bus and electronicsNo
between PROFINET and all other circuitsYes; 1500 V AC (type test)
between supply and all other circuitsNo
Permissible potential difference
between different circuitsSafety extra low voltage SELV
Isolation
Isolation tested with750 V DC (type test) and according to EN 50155 (routine test)
Standards, approvals, certificates
Network loading class3
Railway application
EN 50121-3-2Yes; EMC for rail vehicles
EN 50121-4Yes; EMC for signal and telecommunications systems
EN 50121-5Yes; EMC for fixed installations and railway power supply equipment
EN 50124-1Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV
EN 50125-1Yes; Rail vehicles - see ambient conditions
EN 50125-2Yes; Stationary electrical equipment - see ambient conditions
EN 50125-3Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)
EN 50155Yes; Rail vehicles - temperature class OT4, ST1/ST2, horizontal mounting position
EN 61373Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B
Fire protection acc. to EN 45545-2Yes; For proof of conformity, see Service & Support
Security
PROFINET Security Class1
signed firmware updateYes
securely removing dataYes
data integrityYes
Ambient temperature during operation
horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.70 °C; = Tmax; +85 °C for 10 min (OT4, ST1/ST2 acc. to EN 50155)
vertical installation, min.-40 °C; = Tmin
vertical installation, max.50 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0//6AG1193-6AB00-0AA0)
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according to EN 60721-3-5Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request
— to chemically active substances according to EN 60721-3-5Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-5Yes; Class 5S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-5Yes; Class 5M2 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
— against mechanical environmental conditions in agriculture acc. to ISO 15003Yes; Level 1 (Location LE) using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0/6AG1193-6AB00-0AA0)
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold, fungal and dry rot spores (excluding fauna)
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-6Yes; class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0/6AG1193-6AB00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Electronic equipment on rolling stock acc. to EN 50155Yes; class PC2 protective coating acc. to EN 50155
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
ET-Connection
via BU/BA SendYes; + 16 ET 200AL modules
Mechanics/material
Strain reliefYes; Optional
Dimensions
Width50 mm
Height117 mm
Depth74 mm
Weights
Weight, approx.125 g; without BusAdapter