General information
Product type designationF-RQ 1x24 V DC/24 ... 230 V AC/5 A
based on6ES7136-6RA00-0BF0
usable BaseUnitsBU type F0
Color code for module-specific color-coded labelCC42
Product function
I&M dataYes; I&M0 to I&M3
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Supply voltage
Rated value (DC)24 V; Coil voltage
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
power supply according to NEC Class 2 requiredNo
Power
Power consumption from the backplane bus100 mW
Power loss
Power loss, typ.1 W
Address space per module
Inputs1 byte
Hardware configuration
Automatic encodingYes
Mechanical coding elementYes
Type of mechanical coding elementtype C
Digital outputs
Type of digital outputRelays
Number of digital outputs1
Limitation of inductive shutdown voltage toNo
Controlling a digital inputYes
Switching capacity of the outputs
with resistive load, max.5 A
on lamp load, max.25 W
Switching frequency
with resistive load, max.2 Hz
with inductive load, max.0.1 Hz; See data in manual
with inductive load (acc. to IEC 60947-5-1, DC13), max.0.1 Hz
with inductive load (acc. to IEC 60947-5-1, AC15), max.2 Hz
horizontal installation
— up to 40 °C, max.5 A; note derating data in the manual
— up to 50 °C, max.4 A; note derating data in the manual
— up to 60 °C, max.3 A; note derating data in the manual
— up to 70 °C, max.3 A; note derating information in the manual; only with configured slots to the left and right of the module
vertical installation
— up to 50 °C, max.3 A; note derating data in the manual
Relay outputs
Number of relay outputs1; 2 NO contacts
Rated supply voltage of relay coil L+ (DC)24 V
Current consumption of relays (coil current of all relays), max.70 mA
external protection for relay outputsyes; 6 A, see data in manual
Relay approved acc. to UL 508Yes; Pilot Duty B300, R300
Switching capacity of contacts
— with inductive load, max.see additional description in the manual
— with resistive load, max.see additional description in the manual
— Thermal continuous current, max.5 A
— Switching current, min.1 mA
— Switching current after exceeding 300 mA, min.10 mA
— Switching current after exceeding 300 mA, max.5 A
— Rated switching voltage (DC)24 V
— Rated switching voltage (AC)230 V
Cable length
shielded, max.500 m; for load contacts
unshielded, max.300 m; for load contacts
Control cable (input), max.10 m
Interrupts/diagnostics/status information
Diagnostics functionYes
Diagnostics indication LED
RUN LEDYes; green/red DIAG LED
Channel status displayYes; green LED
Potential separation channels
between the channelsYes; for SELV / PELV only
between the channels and backplane busYes
between the channels and the power supply of the electronicsYes
Permissible potential difference
between channels and backplane bus/supply voltage250 V AC (reinforced insulation)
Isolation
Isolation tested with2 545 V DC (type test) and according to EN 50155 (routine test)
Overvoltage categoryIII (according to IEC/EN 61131-2:2007 and EN 298:2022), II (according to IEC 61131-2:2017 and IEC 61010-2-201)
Standards, approvals, certificates
Suitable for safety functionsYes
Ecological footprint
environmental product declarationYes
Global warming potential
— global warming potential, (total) [CO2 eq]52 kg
— global warming potential, (during production) [CO2 eq]6.8 kg
— global warming potential, (during operation) [CO2 eq]45.8 kg
— global warming potential, (after end of life cycle) [CO2 eq]-0.628 kg
Highest safety class achievable in safety mode
Performance level according to ISO 13849-1PLe
Category according to ISO 13849-14
SIL acc. to IEC 61508SIL 3
SIL in accordance with EN 50126-1, 50129, 50159, 50716SIL 2; a higher safety integrity level is possible if tested and approved for the specific application under consideration of all local regulations.
Probability of failure (for service life of 20 years and repair time of 100 hours)
— Low demand mode: PFDavg in accordance with SIL2< 1.00E-04, function test 1x per year
— Low demand mode: PFDavg in accordance with SIL3< 1.00E-05, function test 1x per month
— High demand/continuous mode: PFH in accordance with SIL2< 1.00E-08 1/h, function test 1x per year
— High demand/continuous mode: PFH in accordance with SIL3< 6.00E-09 1/h, function test 1x per month
Railway application
EN 50121-3-2Yes; EMC for rail vehicles
EN 50121-4Yes; EMC for signal and telecommunications systems
EN 50121-5Yes; EMC for fixed installations and railway power supply equipment (shielded cables required)
EN 50124-1Yes; Railway applications - overvoltage category OV3; pollution degree PD2; UNm = 230 V AC
EN 50125-1Yes; Rail vehicles - see ambient conditions
EN 50125-2Yes; Stationary electrical equipment - see ambient conditions
EN 50125-3Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)
EN 50155Yes; Rail vehicles - temperature class OT1, ST1/ST2, horizontal mounting position
EN 61373Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B
Fire protection acc. to EN 45545-2Yes; For proof of conformity, see Service & Support
Ambient temperature during operation
horizontal installation, min.-30 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.60 °C; = Tmax; +70 °C for 10 min (OT1, ST1/ST2 acc. to EN 50155); +70 °C continuously with spacing modules (6AG2193-6BN00-4BA0) or configured empty slots to the left and right of the module (OT3, ST1/ST2 acc. to EN 50155)
vertical installation, min.-30 °C; = Tmin
vertical installation, max.50 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according to EN 60721-3-5Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request
— to chemically active substances according to EN 60721-3-5Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-5Yes; Class 5S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Electronic equipment on rolling stock acc. to EN 50155Yes; Class PC2 protective coating acc. to EN 50155:2017
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width20 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.56 g
Other
Note:for use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A, Online Support article 109736776