General information
Product type designationF-AI 4XU 0..10V HF
FW update possibleYes
based on6ES7136-6AB00-0CA1
usable BaseUnitsBU type A0, A1
Color code for module-specific color-coded labelCC00
Product function
I&M dataYes; I&M0 to I&M3
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
cyclic measurementYes
OversamplingNo
MSINo
CiR - Configuration in RUN
Reparameterization possible in RUNNo
Calibration possible in RUNNo
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
power supply according to NEC Class 2 requiredNo
Input current
Current consumption (rated value)0.38 A
Current consumption, max.0.4 A
24 V encoder supply
24 VYes; min. L+ (-1.5 V)
Short-circuit protectionYes
Output current, max.300 mA; total current of all encoders/channels
Power
Power consumption from the backplane bus70 mW
Power loss
Power loss, typ.2 W
Address space per module
Inputs14 byte; S7-300/400F CPU, 13 byte
Outputs5 byte; S7-300/400F CPU, 4 byte
Hardware configuration
Automatic encodingYes
Electronic coding element type HYes
Analog inputs
Number of analog inputs4
For voltage measurement4
permissible input voltage for voltage input (destruction limit), max.36 V
Input ranges (rated values), voltages
0 to +10 VYes
— Input resistance (0 to 10 V)16 kΩ
Cable length
shielded, max.200 m
Analog value generation for the inputs
Measurement principleSigma Delta
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Integration time, parameterizableYes
Integration time (ms)20 / 16,667
Interference voltage suppression for interference frequency f1 in Hz50 / 60 Hz
Smoothing of measured values
Number of smoothing levels7
parameterizableYes
Step: NoneYes; 1x conversion cycle time
Step: lowYes; 2x / 4x conversion cycle time
Step: MediumYes; 8x / 16x conversion cycle time
Step: HighYes; 32x / 64x conversion cycle time
Average value filterYes
Connection of signal encoders
for voltage measurementYes
Errors/accuracies
Linearity error (relative to input range), (+/-)0.1 %
Temperature error (relative to input range), (+/-)0.023 %/K
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.1 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)2.6 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.1 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.40 dB
Common mode voltage, max.10 V
Common mode interference, min.70 dB
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Limit value alarmNo
Diagnoses
Monitoring the supply voltageYes
Wire breakYes
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; green/red DIAG LED
Potential separation channels
between the channelsNo
between the channels and backplane busYes
between the channels and the power supply of the electronicsYes
Permissible potential difference
between the inputs (UCM)10 Vpp
Isolation
Isolation tested with750 V DC (type test) and according to EN 50155 (routine test)
Ecological footprint
environmental product declarationYes
Global warming potential
— global warming potential, (total) [CO2 eq]88.3 kg
— global warming potential, (during production) [CO2 eq]13.1 kg
— global warming potential, (during operation) [CO2 eq]76.6 kg
— global warming potential, (after end of life cycle) [CO2 eq]-1.37 kg
Highest safety class achievable in safety mode
Performance level according to ISO 13849-1PLe
Category according to ISO 13849-1Cat. 4
SIL acc. to IEC 61508SIL 3
SIL in accordance with EN 50126-1, 50129, 50159, 50716SIL 2; a higher safety integrity level is possible if tested and approved for the specific application under consideration of all local regulations.
Probability of failure (for service life of 20 years and repair time of 100 hours)
— Low demand mode: PFDavg in accordance with SIL3< 5.00E-05
— High demand/continuous mode: PFH in accordance with SIL3< 1.00E-09 1/h
Railway application
EN 50121-3-2Yes; EMC for rail vehicles
EN 50121-4Yes; EMC for signal and telecommunications systems
EN 50121-5Yes; EMC for fixed installations and railway power supply equipment
EN 50124-1Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC
EN 50125-1Yes; Rail vehicles - see ambient conditions
EN 50125-2Yes; Stationary electrical equipment - see ambient conditions
EN 50125-3Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)
EN 50155Yes; Rail vehicles - temperature class OT1, ST1/ST2, horizontal mounting position
EN 61373Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B
Fire protection acc. to EN 45545-2Yes; For proof of conformity, see Service & Support
Ambient temperature during operation
horizontal installation, min.-30 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.60 °C; = Tmax; +70 °C for 10 min (OT1, ST1/ST2 acc. to EN 50155); +70 °C continuously with spacing modules (6AG2193-6BN00-4BA0) or configured empty slots to the left and right of the module (OT3, ST1/ST2 acc. to EN 50155)
vertical installation, min.-30 °C; = Tmin
vertical installation, max.50 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according to EN 60721-3-5Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request
— to chemically active substances according to EN 60721-3-5Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-5Yes; Class 5S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-5Yes; Class 5M2 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
— against mechanical environmental conditions in agriculture acc. to ISO 15003Yes; level 1 (Location LE) using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Electronic equipment on rolling stock acc. to EN 50155Yes; Class PC2 protective coating acc. to EN 50155:2017
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width15 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.48 g
Other
Note:for use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A, Online Support article 109736776