product brand nameSIPLUS
transfer rate
for Industrial Ethernet10 ... 100 Mbit/s
according to RS 23250 ... 38400 bit/s
interfaces
number of interfaces / according to Industrial Ethernet2
for external data transmission / according to RS 2322
for power supply1
of Industrial Ethernet interfaceRJ45 port
at interface 1 / for external data transmission9 pin Sub-D-connector, RS232 switchable to RS485
at interface 2 / for external data transmission9-pole D-sub connector, RS232 can be switched to RS485
for power supply2-pole plugable terminal block
C-PLUGYes
supply voltage, current consumption, power loss
type of voltage / of the supply voltageDC
supply voltage24 V
supply voltage20.4 ... 28.8 V
supply voltage / external / at DC / rated value24 V
supply voltage / external / at DC / rated value20.4 ... 28.8 V
from backplane bus / at DC / at 24 V / maximum0.2 A
from external supply voltage / at DC / at 24 V / maximum0.17 A
power loss [W]4.6 W
product extension / optional / backup batteryYes
type of batteryLithium AA / 3.6 V / 2.3 Ah
typical100 µA
maximum160 µA
ambient conditions
during operation-25 ... +70 °C
during storage-40 ... +70 °C
during transport-40 ... +70 °C
installation altitude / at height above sea level / maximum5000 m
ambient condition / relating to ambient temperature - air pressure - installation altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
with condensation / according to IEC 60068-2-38 / maximum100 %; RH including condensation/frost (no commissioning when condensation is present), horizontal installation
chemical resistance / to commercially available cooling lubricantsYes; incl. airborne diesel and oil droplets
conformity according to EN 60721-3-3Yes; Class 3B2 mold and fungal spores (excluding fauna), Class 3B3 on request
conformity according to EN 60721-3-6Yes; Class 6B2 mold, fungal and dry rot spores (excluding fauna)
conformity according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray in accordance with EN 60068-2-52 (Severity 3). The supplied plug covers must remain in place on the unused interfaces during operation.
conformity according to EN 60721-3-6Yes
conformity according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation.
conformity according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation.
coating / for equipped printed circuit board / according to EN 61086Yes; Class 2 for high availability
type of coating / protection against pollution according to EN 60664-3Yes; Protection of the type 1
type of test / of the coating / according to MIL-I-46058CYes; Coating discoloration during service life possible
product conformity / of the coating / Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, class A
protection class IPIP20
design, dimensions and weights
module formatCompact module S7-300 double width
width80 mm
height125 mm
depth120 mm
net weight0.4 kg
product features, product functions, product components / general
with RS 232 interface / maximum6 m
with RS 485 interface / maximum30 m
performance data / S7 communication
maximum64
with PG connections / maximum2
with OP connections / maximum62
SINAUT ST7 via S7 communicationYes
PG/OP communicationYes
performance data / multi-protocol mode
number of active connections / with multi-protocol mode128
performance data / telecontrol
node stationYes
substationYes
TIM control centerYes
SINAUT ST1 protocolYes
SINAUT ST7 protocolYes
noteTD7onCPU: at least 20 KB, actual requirement determined by data volume and functional scope TD7onTIM: 0 bytes in most favorable case
product feature / buffered message frame memoryYes
for SINAUT ST1 protocol with polling / 11 bitYes
for SINAUT ST1 protocol with spontaneous / 10-bit or 11-bitYes
for SINAUT ST7 protocol with multi-master polling / 10-bitYes
for SINAUT ST7 protocol with polling or spontaneous / 10-bit or 11-bitYes
with dedicated line/radio link / with SINAUT ST1 protocolPolling, polling with time slot procedure
with dedicated line/radio link / with SINAUT ST7 protocolPolling, polling with time slot procedure, multi-master polling with time slot procedure
with dial-up network / with SINAUT ST1 protocolspontaneous
with dial-up network / with SINAUT ST7 protocolspontaneous
for SINAUT ST1 protocol4
for SINAUT ST7 protocol4
product functions / management, configuration, engineering
requiredSINAUT ST7 ES
for CPU configuring / required / SINAUT TD7 block library for CPUYes
for PG configuring / required / SINAUT ST7 configuration software for PGYes
storage location / of TIM configuration dataon internal TIM flash memory, or on TIM in optional C‑PLUG, or on MMC of the S7-300 CPU if TIM installed in S7-300 controller
product functions / security
operating mode / Virtual Private Network (VPN)Yes
type of authentication / with Virtual Private Network / PSKYes
with Virtual Private Network MSC / is supportedTCP/IP
product functions / time
product component / hardware real time clockYes
product feature / hardware real time clock w. battery backupYes
accuracy / of the hardware real time clock / per day / maximum4 s