General information
based on6ES7432-1HF00-0AB0
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from supply and load voltage L+ (without load), max.200 mA; at rated load: max. 400 mA
from backplane bus 5 V DC, max.150 mA
Power loss
Power loss, typ.9 W
Analog outputs
Number of analog outputs8
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.30 mA
Current output, no-load voltage, max.19 V
Output ranges, voltage
0 to 10 VYes
1 V to 5 VYes
-10 V to +10 VYes
Output ranges, current
0 to 20 mAYes
-20 mA to +20 mAYes
4 mA to 20 mAYes
Connection of actuators
for voltage output two-wire connectionYes; possible, without compensation of the line resistances
for voltage output four-wire connectionYes; possible
for current output two-wire connectionYes; possible
Load impedance (in rated range of output)
with voltage outputs, min.1 kΩ
with voltage outputs, capacitive load, max.1 µF
with current outputs, max.500 Ω; 600 ohms if common-mode-voltage reduced to <1 V
Cable length
shielded, max.200 m
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.13 bit
Conversion time (per channel)420 µs; 420 µs in the ranges 1 to 5 V and 4 to 20 mA; 300 µs in all ranges
Settling time
for resistive load0.1 ms
for capacitive load3.5 ms
for inductive load0.5 ms
Operational error limit in overall temperature range
Voltage, relative to output range, (+/-)0.5 %; ±10 V, 0 to 10 V, 1 to 5 V
Current, relative to output range, (+/-)1 %; ±20 mA, 4 to 20 mV
Basic error limit (operational limit at 25 °C)
Voltage, relative to output range, (+/-)0.5 %; ±10 V, 0 to 10 V, 1 to 5 V
Current, relative to output range, (+/-)0.5 %; ±20 mA, 0 to 20 mA
Interrupts/diagnostics/status information
Diagnostics functionNo
Potential separation analog outputs
between the channelsNo
between the channels and backplane busYes
Isolation
Isolation tested with2 120 V DC between bus and L+/M; 2 120 V DC between bus and analog section; 500 V DC between bus and local ground; 500 V DC between analog section and L+/M; 2 120 V DC between analog section and local ground; 2 120 V DC between L+/M and local ground
Ambient temperature during operation
min.0 °C; = Tmin
max.60 °C; = Tmax
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width25 mm
Height290 mm
Depth210 mm
Weights
Weight, approx.650 g