product brand nameSIPLUS
suitability for operationGateway between Industrial Ethernet and PROFIBUS
transfer rate
at the 1st interface10 ... 100 Mbit/s
at the 2nd interface0.0096 ... 12 Mbit/s
interfaces
at the 1st interface / according to Industrial Ethernet2
at the 2nd interface / according to PROFIBUS1
for power supply2
at the 1st interface / according to Industrial EthernetRJ45 port onboard or bus adapter
at the 2nd interface / according to PROFIBUS9-pin Sub-D socket (RS 485)
for power supply4-pole terminal block
C-PLUGYes
supply voltage, current consumption, power loss
type of voltage / of the supply voltageDC
supply voltage / external / at DC / rated value24 V
relative positive tolerance / at DC / at 24 V20 %
relative negative tolerance / at DC / at 24 V15 %
from external supply voltage / at DC / at 24 V / typical0.2 A
from external supply voltage / at DC / at 24 V / maximum0.3 A
power loss [W]4.8 W; Typical
ambient conditions
for vertical installation / during operation-40 ... +40 °C
for horizontally arranged busbars / during operation-40 ... +60 °C
during storage-40 ... +70 °C
during transport-40 ... +70 °C
installation altitude / at height above sea level / maximum5000 m
ambient condition / relating to ambient temperature - air pressure - installation altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
with condensation / according to IEC 60068-2-38 / maximum100 %; RH including condensation/frost (no commissioning when condensation is present), horizontal installation
chemical resistance / to commercially available cooling lubricantsYes; incl. airborne diesel and oil droplets
conformity according to EN 60721-3-3Yes; Class 3B2 mold and fungal spores (excluding fauna), Class 3B3 on request
conformity according to EN 60721-3-6Yes; Class 6B2 mold, fungal and dry rot spores (excluding fauna)
conformity according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray in accordance with EN 60068-2-52 (Severity 3). The supplied plug covers must remain in place on the unused interfaces during operation.
conformity according to EN 60721-3-6Yes
conformity according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation.
conformity according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation.
coating / for equipped printed circuit board / according to EN 61086Yes; Class 2 for high availability
type of coating / protection against pollution according to EN 60664-3Yes; Protection of the type 1
type of test / of the coating / according to MIL-I-46058CYes; Coating discoloration during service life possible
product conformity / of the coating / Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, class A
protection class IPIP20
design, dimensions and weights
module formatET 200SP design
width100 mm
height117 mm
depth74 mm
net weight0.6 kg
35 mm DIN-rail mountingYes
performance data / PROFIBUS DP
DPV0Yes
DPV1Yes
at the 2nd interface / as DP master / maximum64
of the address range of the inputs / as DP master / total2048 byte
of the address range of the outputs / as DP master / total2048 byte
of the address range of the inputs / per DP device244 byte
of the address range of the outputs / per DP device244 byte
performance data / S7 communication
maximum32
performance data / multi-protocol mode
number of active connections / with multi-protocol mode48
performance data / PROFINET communication / as PN IO device
product function / PROFINET IO deviceYes
product functions / management, configuration, engineering
product function / MIB supportYes
SNMP v1Yes
DCPYes
LLDPYes
I&M0 - device-specific informationYes
I&M1 - higher level designation/location designationYes
I&M2 - installation dateYes
I&M3 - commentYes
product functions / routing
service / as PROFIBUS / dataset routingYes
number of possible connections / with dataset routing / maximum32
product functions / redundancy
ring redundancyYes
PROFINET system redundancyNo
protocol / is supported / Media Redundancy Protocol (MRP)Yes
product functions / time
product function / pass on time synchronizationYes
NTPYes
SIMATIC time synchronization (SIMATIC Time)Yes
standards, specifications, approvals / hazardous environments / header
certificate of suitability / CCC / for hazardous zone according to GB standardYes
accessories
accessoriesOptional: C-PLUG, BusAdapter of the ET 200SP system