General information
based on6ES7332-5HB01-0AB0
Product function
Isochronous modeNo
Load voltage L+
Rated value (DC)24 V; A power supply according to EN 50155 shall be used for railway applications
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.135 mA
from backplane bus 5 V DC, max.60 mA
Power loss
Power loss, typ.3 W
Analog outputs
Number of analog outputs2
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.25 mA
Current output, no-load voltage, max.18 V
Output ranges, voltage
0 to 10 VYes
1 V to 5 VYes
-10 V to +10 VYes
Output ranges, current
0 to 20 mAYes
-20 mA to +20 mAYes
4 mA to 20 mAYes
Connection of actuators
for voltage output two-wire connectionYes
for voltage output four-wire connectionYes
for current output two-wire connectionYes
Load impedance (in rated range of output)
with voltage outputs, min.1 kΩ
with voltage outputs, capacitive load, max.1 µF
with current outputs, max.500 Ω
with current outputs, inductive load, max.10 mH
Cable length
shielded, max.200 m
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit; ±10 V, ±20 mA, 4 mA to 20 mA, 1 V to 5 V: 11 bit + sign; 0 V to 10 V, 0 mA to 20 mA: 12 bit
Conversion time (per channel)0.8 ms
Settling time
for resistive load0.2 ms
for capacitive load3.3 ms
for inductive load0.5 ms; 0.5 ms (1 mH); 3.3 ms (10 mH)
Operational error limit in overall temperature range
Voltage, relative to output range, (+/-)0.5 %; ±0.6 % @ < 0 °C or > 60 °C
Current, relative to output range, (+/-)0.6 %; ±0.7 % @ < 0 °C or > 60 °C
Basic error limit (operational limit at 25 °C)
Voltage, relative to output range, (+/-)0.4 %
Current, relative to output range, (+/-)0.5 %
Interrupts/diagnostics/status information
Diagnostics functionYes; Parameterizable
Substitute values connectableYes; Parameterizable
Alarms
Diagnostic alarmYes; Parameterizable
Diagnoses
Diagnostic information readableYes
Diagnostics indication LED
Group error SF (red)Yes
Potential separation analog outputs
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+Yes
between the channels and the power supply of the electronicsYes
Isolation
Isolation tested with500 V DC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Railway application
EN 50155Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B, EN 50155:2007 (see SIOS entry 109755985)
Ambient temperature during operation
min.-25 °C; = Tmin
max.70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according to EN 60721-3-5Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request
— to chemically active substances according to EN 60721-3-5Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 50155 (ST2); *
— to mechanically active substances according to EN 60721-3-5Yes; Class 5S3 incl. sand, dust; *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.220 g