General information
based on6ES7331-1KF02-0AB0
Product function
Isochronous modeNo
Input current
from backplane bus 5 V DC, max.90 mA
Power loss
Power loss, typ.0.4 W
Analog inputs
Number of analog inputs8
For resistance measurement8
permissible input voltage for voltage input (destruction limit), max.30 V; 12 V continuous, 30 V for max. 1 s
permissible input current for current input (destruction limit), max.40 mA
Input ranges
VoltageYes
CurrentYes
ThermocoupleNo
Resistance thermometerYes
ResistanceYes
Input ranges (rated values), voltages
0 to +10 VYes
— Input resistance (0 to 10 V)100 kΩ
1 V to 5 VYes
— Input resistance (1 V to 5 V)100 kΩ
1 V to 10 VNo
-1 V to +1 VYes
— Input resistance (-1 V to +1 V)100 kΩ
-10 V to +10 VYes
— Input resistance (-10 V to +10 V)100 kΩ
-2.5 V to +2.5 VNo
-250 mV to +250 mVNo
-5 V to +5 VYes
— Input resistance (-5 V to +5 V)100 kΩ
-50 mV to +50 mVYes
— Input resistance (-50 mV to +50 mV)100 kΩ
-500 mV to +500 mVYes
— Input resistance (-500 mV to +500 mV)100 kΩ
-80 mV to +80 mVNo
Input ranges (rated values), currents
0 to 20 mAYes
— Input resistance (0 to 20 mA)100 Ω
-10 mA to +10 mANo
-20 mA to +20 mAYes
— Input resistance (-20 mA to +20 mA)100 Ω
-3.2 mA to +3.2 mANo
4 mA to 20 mAYes
— Input resistance (4 mA to 20 mA)100 Ω
Input ranges (rated values), thermocouples
Type BNo
Type CNo
Type ENo
Type JNo
Type KNo
Type LNo
Type NNo
Type RNo
Type SNo
Type TNo
Type UNo
Type TXK/TXK(L) to GOSTNo
Input ranges (rated values), resistance thermometer
Cu 10No
Ni 100Yes; Standard/climate
— Input resistance (Ni 100)100 MΩ
Ni 1000Yes
— Input resistance (Ni 1000)100 MΩ
LG-Ni 1000Yes; Standard/climate
— Input resistance (LG-Ni 1000)100 MΩ
Ni 120No
Ni 200No
Ni 500No
Pt 100Yes; Standard/climate
— Input resistance (Pt 100)100 MΩ
Pt 1000No
Pt 200No
Pt 500No
Input ranges (rated values), resistors
0 to 150 ohmsNo
0 to 300 ohmsNo
0 to 600 ohmsYes
— Input resistance (0 to 600 ohms)100 MΩ
0 to 6000 ohmsYes
— Input resistance (0 to 6000 ohms)100 MΩ
Characteristic linearization
ParameterizableYes
— for resistance thermometeryes; Pt100 standard/air con.; Ni100 standard/air con.; Ni1000 standard/air con.; LG-Ni1000 standard/air con.
Cable length
shielded, max.200 m; max. 50 m at 50 mV
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.13 bit
Integration time, parameterizableYes; 60 / 50 ms
Basic conversion time (ms)66 / 55 ms
Interference voltage suppression for interference frequency f1 in Hz50 / 60 Hz
Connection of signal encoders
for voltage measurementYes
for current measurement as 2-wire transducerYes; with external supply
for current measurement as 4-wire transducerYes
for resistance measurement with two-wire connectionYes
for resistance measurement with three-wire connectionYes
for resistance measurement with four-wire connectionYes
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0.6 %; ±0.6 % (±5 V, 10 V, 1 to 5 V, 0 to 10 V); ±0.5 % (±50 mV, 500 mV, 1 V) @ 0 ... +60 °C; ±0.7 % (±5 V, 10 V, 1 to 5 V, 0 to 10 V); ±0.6 % (±50 mV, 500 mV, 1 V) @ -25 ... +70 °C
Current, relative to input range, (+/-)0.5 %; @ 0 ... +60 °C; ±0.6% @ -25 ... +70 °C; ±20 mA, 0 to 20 mA, 4 to 20 mA
Resistance, relative to input range, (+/-)0.5 %; @ 0 ... +60 °C; 0.6% @ -25 ... +70 °C; 0 to 6 kohm, 0 to 600 kohm
Resistance thermometer, relative to input range, (+/-)1 Kelvin (Pt100, Ni100, climate; Ni1000, LG-Ni1000, standard; Ni1000, LG-Ni1000, climate); 1.2 Kelvin (Pt100, Ni100, standard) @ 0 ... +60 °C; 1.2 Kelvin (Pt100, Ni100, climate; Ni1000, LG-Ni1000, standard; Ni1000, LG-Ni1000, climate); 1.4 Kelvin (Pt100, Ni100, standard) @ -25 ... +70 °C
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.4 %; 0.4% (±5 V, 10 V, 1 to 5 V, 0 to 10 V); 0.3% (±50 mV, 500 mV, 1 V)
Current, relative to input range, (+/-)0.3 %; ±20 mA, 0 to 20 mA, 4 to 20 mA
Resistance, relative to input range, (+/-)0.3 %; 0 to 6 kohms, 0 to 600 kohms
Resistance thermometer, relative to input range, (+/-)1 Kelvin (Pt100, Ni100, standard); 0.8 Kelvin (Pt100, Ni100, climatic; Ni1000, LG-Ni1000, standard; Ni1000, LG-Ni1000, climatic)
Interrupts/diagnostics/status information
Diagnostics functionNo
Alarms
Diagnostic alarmNo
Limit value alarmNo
Diagnoses
Diagnostic information readableNo
Diagnostics indication LED
Group error SF (red)No
Potential separation analog inputs
between the channelsNo
between the channels and backplane busYes
Isolation
Isolation tested with500 V DC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Railway application
EN 50121-4No
EN 50155No
Ambient temperature during operation
min.-25 °C
max.70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector40-pin
Dimensions
Width40 mm
Height125 mm
Depth117 mm
Weights
Weight, approx.250 g