General information
based on6ES7322-1FH00-0AA0
Load voltage L1
Rated value (AC)230 V; 120/230 V AC
permissible range, lower limit (AC)79 V
permissible range, upper limit (AC)264 V
Input current
from load voltage L1 (without load), max.2 mA
from backplane bus 5 V DC, max.200 mA
Power loss
Power loss, typ.8.6 W
Digital outputs
Number of digital outputs16
Short-circuit protectionYes; Fuse 8 A, 250 V; per group
required current for fuse shutdown, min.40 A
Response time, max.300 ms
Controlling a digital inputYes
Size of motor starters according to NEMA, max.4 NEMA compliant
Spare fuses8 A / quick response
Switching capacity of the outputs
on lamp load, max.50 W
Output voltage
for signal "1" (at max. current), min.L1 (-1.5 V)
for signal "1" (at min. current), min.L1 (-8.5 V)
Output current
for signal "1" rated value1 A
for signal "1" permissible range for 0 to 40 °C, min.10 mA
for signal "1" permissible range for 0 to 40 °C, max.1 A
for signal "1" permissible range for 40 to 60 °C, min.10 mA
for signal "1" permissible range for 40 to 60 °C, max.0.5 A
for signal "1" minimum load current10 mA
for signal "1" permissible surge current, max.20 A; with 2 half waves
for signal "0" residual current, max.2 mA
Parallel switching of two outputs
for upratingNo
for redundant control of a loadYes; only outputs of the same group
Switching frequency
with resistive load, max.10 Hz
with inductive load, max.0.5 Hz
with inductive load (acc. to IEC 60947-5-1, AC15), max.0.5 Hz
on lamp load, max.1 Hz
horizontal installation
— up to 40 °C, max.4 A
— up to 60 °C, max.2 A
— up to 70 °C, max.1 A
vertical installation
— up to 40 °C, max.2 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Interrupts/diagnostics/status information
Diagnostics functionYes; Fuse blown or load voltage missing
Alarms
Diagnostic alarmNo
Diagnoses
Wire breakNo
Short-circuitNo
Fuse blownYes
Missing load voltageNo
Diagnostics indication LED
Rated load voltage PWR (green)No
Fuse OK FSG (green)Yes; Red LED for fuse
Group error SF (red)Yes
Status indicator digital output (green)Yes
Potential separation digital outputs
between the channels, in groups of8
between the channels and backplane busYes; Optocoupler
Isolation
Isolation tested with4 000 V DC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Railway application
EN 50121-4No
EN 50155No
Ambient temperature during operation
min.-40 °C; = Tmin
max.70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.275 g