General information
based on6ES7322-1FF01-0AA0
Load voltage L1
Rated value (AC)230 V; 120/230 V AC
permissible range, lower limit (AC)93 V
permissible range, upper limit (AC)264 V
permissible frequency range, lower limit47 Hz
permissible frequency range, upper limit63 Hz
Input current
from load voltage L1 (without load), max.2 mA
from backplane bus 5 V DC, max.100 mA
Power loss
Power loss, typ.8.6 W
Digital outputs
Number of digital outputs8
Short-circuit protectionYes; Fuse 8 A, 250 V; per group
required current for fuse shutdown, min.40 A
Response time, max.300 ms
Controlling a digital inputYes
Size of motor starters according to NEMA, max.5 NEMA compliant
Spare fuses8 A / quick response
Zero-crossing switchYes; Max. 60 V
Switching capacity of the outputs
on lamp load, max.50 W
Output voltage
for signal "1", min.L1 (-1.5 V)
for signal "1" (at max. current), min.L1 (-1.5 V)
for signal "1" (at min. current), min.L1 (-8.5 V)
Output current
for signal "1" rated value2 A
for signal "1" permissible range for 0 to 40 °C, min.10 mA
for signal "1" permissible range for 0 to 40 °C, max.2 A
for signal "1" permissible range for 40 to 60 °C, min.10 mA
for signal "1" permissible range for 40 to 60 °C, max.1 A
for signal "1" minimum load current10 mA
for signal "1" permissible surge current, max.20 A; max. 1 AC cycle
for signal "0" residual current, max.2 mA
Output delay with resistive load
"0" to "1", max.1 AC cycle
"1" to "0", max.1 AC cycle
Parallel switching of two outputs
for upratingNo
for redundant control of a loadYes
Switching frequency
with resistive load, max.10 Hz
with inductive load, max.0.5 Hz
with inductive load (acc. to IEC 60947-5-1, AC15), max.0.5 Hz
on lamp load, max.1 Hz
horizontal installation
— up to 40 °C, max.4 A
— up to 60 °C, max.2 A
— up to 70 °C, max.1.5 A
vertical installation
— up to 40 °C, max.2 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Interrupts/diagnostics/status information
AlarmsNo
Diagnostics functionYes; Fuse blown or load voltage missing
Alarms
Diagnostic alarmNo
Diagnoses
Wire breakNo
Short-circuitNo
Fuse blownYes
Missing load voltageYes
Diagnostics indication LED
Rated load voltage PWR (green)Yes
Fuse OK FSG (green)Yes
Group error SF (red)Yes
Status indicator digital output (green)Yes
Potential separation digital outputs
between the channelsYes
between the channels, in groups of4
between the channels and backplane busYes; Optocoupler
Isolation
Isolation tested with1 500 V AC
Standards, approvals, certificates
CE markYes
UL approvalYes; File E239877
RCM (formerly C-TICK)Yes
KC approvalYes
EAC (formerly Gost-R)Yes
Railway application
EN 50155Yes; T1 Category 1 Class A/B horizontal mounting position
Ambient temperature during operation
min.-40 °C
max.70 °C; = Tmax; for use on railway vehicles according to EN 50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/UL hazardous use applies
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.275 g