General information
Product type designationPM240-2
Product versionFSF 132 kW
Design of the converterFSF
based on6SL3210-1PE32-5UL0
Protection function
Undervoltage protectionYes
Overvoltage protectionYes
Overload protectionYes
Ground-fault protectionYes
short-circuit protectionYes
Stall protectionYes
With blocked rotorYes
Temperature monitor for motorYes
Temperature monitor for converterYes
Parameter lockingYes
Input voltage
Type of input voltageAC
Mains filter
presentNo
Input current
Input current with low overload242 A
Input current with high overload218 A
Output voltage
Output voltage in relation to input voltage, min.0 %
Output voltage in relation to input voltage, max.95 %
Pulse frequency2 kHz
Output current
Output current, max.410 A
Output current without overload250 A
Output current with low overload250 A
Output current with high overload205 A
Power loss
Power loss, max.2.809 kW
Power loss of the CDM in standby mode48.1 W
Power loss of the CDM at the operating point (0/25)747.1 W
Power loss of the CDM at the operating point (0/50)1 054.9 W
Power loss of the CDM at the operating point (0/100)2 010.4 W
Power loss of the CDM at the operating point (50/25)810.2 W
Power loss of the CDM at the operating point (50/50)1 202.7 W
Power loss of the CDM at the operating point (50/100)2 411.6 W
Power loss of the CDM at the operating point (90/50)1 421.4 W
Power loss of the CDM at the operating point (90/100)3 090.2 W
Relative power loss of the CDM at the operating point (0/25)0.43 %
Relative power loss of the CDM at the operating point (0/50)0.61 %
Relative power loss of the CDM at the operating point (0/100)1.16 %
Relative power loss of the CDM at the operating point (50/25)0.47 %
Relative power loss of the CDM at the operating point (50/50)0.69 %
Relative power loss of the CDM at the operating point (50/100)1.39 %
Relative power loss of the CDM at the operating point (90/50)0.82 %
Relative power loss of the CDM at the operating point (90/100)1.78 %
Ratio of converter losses / reference converter losses at the operating point (90/100)0.44
IE class of the CDMIE2
Power electronics
emitted active power with low overload132 kW
emitted active power with high overload110 kW
active power output with low overload [hp]200 hp
active power output with high overload [hp]150 hp
apparent power output173.21 kVA
Efficiency0.98
Type of duty cycle duration with low overload1.1x rated output current (i.e. 110 % overload) for 57 s with a cycle time of 300 s; 1.5x rated output current (i.e. 150 % overload) for 3 s with a cycle time of 300 s
Type of duty cycle duration with high overload1.5x output current rating (i.e. 150 % overload) for 57 s with a cycle time of 300 s; 2x output current rating (i.e. 200 % overload) for 3 s with a cycle time of 300 s
Cooling methodInternal air cooling
Cooling air flow0.153 m³/s
Short-time withstand current (SCCR) of the entire control cabinet in accordance with UL 508A65 kA
Isolation
Degree of pollution2 according to EN 61800-5-1
Degree and class of protection
IP degree of protectionIP20
Equipment protection class according to EN 61800-5-1Class I (with protective bonding circuit) and Class III (PELV)
Touch protection according to EN 61800-5-1Assuming use as prescribed
Standards, approvals, certificates
Certificate of suitabilityCE / TÜV
Standard for EMC according to EN 61800-3the EMC product standard EN 61800-3 does not apply directly to a frequency inverter but to a PDS (Power Drive System), which comprises the complete circuitry, motor and cables in addition to the inverter
Ambient temperature during operation
min.-20 °C; = Tmin
max.50 °C; = Tmax
Ambient temperature during storage/transportation
Storage, min.-25 °C
Storage, max.55 °C
Storage, min. [°F]-13 °F
Storage, max. [°F]131 °F; Class 1K3 acc. to EN 60721-3-1
Transportation, min.-40 °C
Transportation, max.70 °C
Transport, min. [°F]-40 °F
Transport, max. [°F]158 °F; Class 2K3 according to EN 60721-3-2
Altitude during operation relating to sea level
Installation altitude above sea level without derating, max.1 000 m
Relative humidity
Operation, max.98 %
Condensation permissibleNo
Vibrations
Vibration frequency with constant acceleration during operation according to EN 60068-2-6, min.10 Hz
Vibration frequency with constant acceleration during operation according to EN 60068-2-6, max.200 Hz; Constant acceleration = 9.81 m/s² (1 g)
Vibration frequency with constant deflection during operation according to EN 60068-2-6, min.13 Hz
Vibration frequency with constant deflection during operation according to EN 60068-2-6, max.58 Hz; Constant deflection 0.075 mm
Oscillation frequency during transport in accordance with EN 60721-3-2Class 2M3
Shock testing
Shock load during operation(15x g)/11 ms
Shock acceleration during operation according to EN 60068-2-27147 m/s²
Shock acceleration during transport according to EN 60721-3-2Class 2M3
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3No
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Cables
Cable length for motor, shielded, max.300 m
Cable length for braking resistor, max.10 m
Connection method
Design of electrical connection of motorM10 screw stud
connectable cable cross-section for motor supply line, min.35 mm²
connectable cable cross-section for motor supply line, max.120 mm²
Connectable conductor cross-section for AWG cables, min.2
Type of electrical connection for mains supply lineM10 screw stud
connectable cable cross-section for mains supply line, min.35 mm²
connectable cable cross-section for mains supply line, max.120 mm²
Connectable conductor cross-section for AWG cables, min.2
Type of electrical connection for supply cable to braking resistorScrew terminals
Connectable cable cross-section for supply cable to braking resistor, min.25 mm²
Connectable cable cross-section for supply cable to braking resistor, max.70 mm²
Connectable conductor cross-section for AWG cables, min.4
Design of electrical connection for the PE conductorM10 screw stud
Dimensions
Width305 mm
Height708 mm
Depth357 mm
Weights
Weight (without packaging)61 kg
Other
Sound pressure level (1 m), max.67.7 dB
Brake designDC braking, compound braking, resistance braking with integrated brake chopper (for size FSGX optional)