General information
Product type designationAI 2xSG 4-/6-wire HS
FW update possibleYes
based on7MH4134-6LB00-0DA0
usable BaseUnitsBU type A0
Color code for module-specific color-coded labelCC00
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeYes
Measuring range scalableYes
Scalable measured valuesNo
Adjustment of measuring rangeYes; ±0.5 ... 320 mV/V
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
OversamplingYes; 2 channels per module
MSINo
CiR - Configuration in RUN
Reparameterization possible in RUNYes
Calibration possible in RUNNo
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption (rated value)70 mA
Encoder supply
Output voltage (DC)4.85 V
Short-circuit protectionYes
Output current
Rated value60 mA; Per channel
Power
Power consumption from the backplane bus65 mW
Power loss
Power loss, typ.1.5 W
Address space per module
Address space per module, max.32 byte
Inputs32 byte
Outputs8 byte
Hardware configuration
Automatic encodingYes
Mechanical coding elementYes
Type of mechanical coding elementType A
Analog inputs
Number of analog inputs2; Differential inputs
Cycle time (all channels), min.100 µs
Analog input with oversamplingYes
Values per cycle, max.14
Resolution, min.100 µs
Input ranges
Strain gauges (full bridges)Yes
Cable length
shielded, max.500 m
Analog value generation for the inputs
Measurement principleSigma Delta
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.28 bit; 16 bits with oversampling
Integration time, parameterizableYes
Interference voltage suppression for interference frequency f1 in Hz60 / 50 Hz / no
Conversion time (per channel)100 µs
Smoothing of measured values
IIR low-pass filter frequency0.01 ... 600 Hz
IIR low-pass filter ordinal number1 ... 4
Notch filter frequency0.1 ... 1 000 Hz
Notch filter quality5.00 ... 250.00
Average value filter0.1 ... 655.3 ms
Connection of signal encoders
For strain gauges (full bridges) with 4-conductor connectionYes
For strain gauges (full bridges) with 6-conductor connectionYes
Resistance of full bridge, min.80 Ω
Resistance of full bridge, max.5 000 Ω
Errors/accuracies
Linearity error (relative to input range), (+/-)0.025 %
Temperature error (relative to input range), (+/-)0.0005 %/°C; Strain gauge full bridge, 6-conductor connection
Temperature coefficient, zero point≤ ±0.25 μV/K
Temperature coefficient, span, 4-wire connection (in relation to end value)≤ ±5 ppm/K
Temperature coefficient, span, 6-wire connection (in relation to end value)≤ ±10 ppm/K
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.05 %; See manual for details
Isochronous mode
Filtering and processing time (TCI), min.87 µs
Bus cycle time (TDP), min.125 µs
Interrupts/diagnostics/status information
Diagnostics functionYes; Diagnostic alarm
Alarms
Diagnostic alarmYes; Parameterizable
Limit value alarmYes; two upper and two lower limit values in each case
Diagnoses
Monitoring the supply voltageYes
Wire breakYes
Short-circuitYes
Group errorYes
Overflow/UnderflowYes
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; green/red DIAG LED
Potential separation channels
between the channelsNo
between the channels and backplane busYes
between the channels and the power supply of the electronicsYes
Isolation
Isolation tested with707 V DC (type test)
Ambient temperature during operation
horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.60 °C; = Tmax; +70 °C with spacing modules (6AG1193-6BN00-7BA0) or configured slots to the left and right of the module
vertical installation, min.-40 °C; = Tmin
vertical installation, max.50 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75%) incl. salt spray acc. to EN 60068-2-52 (severity degree 3)
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0//6AG1193-6AB00-0AA0)
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold, fungal and dry rot spores (excluding fauna)
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75%) incl. salt spray acc. to EN 60068-2-52 (severity degree 3).
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust
— Against mechanical environmental conditions acc. to EN 60721-3-6Yes; class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0/6AG1193-6AB00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width15 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.30 g