General information
Product type designationAI 4x U/I 2-wire
FW update possibleYes
based on6ES7134-6HD01-0BA1
usable BaseUnitsBU type A0, A1
Color code for module-specific color-coded labelCC03
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
Measuring range scalableNo
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
OversamplingNo
MSINo
CiR - Configuration in RUN
Reparameterization possible in RUNYes
Calibration possible in RUNNo
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption, max.37 mA; without sensor supply
24 V encoder supply
24 VYes
Short-circuit protectionYes
Output current, max.20 mA; max. 50 mA per channel for a duration < 10 s
Power loss
Power loss, typ.0.85 W; Without encoder supply voltage
Address space per module
Address space per module, max.8 byte; + 1 byte for QI information
Hardware configuration
Automatic encodingYes
Mechanical coding elementYes
Type of mechanical coding elementType A
Selection of BaseUnit for connection variants
2-wire connectionBU type A0, A1
Analog inputs
Number of analog inputs4; > 60 °C max. 1x ±20 mA or 4x ±10 V permissible
permissible input voltage for voltage input (destruction limit), max.30 V
permissible input current for current input (destruction limit), max.50 mA
Cycle time (all channels), min.Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels)
Input ranges (rated values), voltages
0 to +10 VYes; 15 bit
— Input resistance (0 to 10 V)120 kΩ
1 V to 5 VYes; 15 bit
— Input resistance (1 V to 5 V)120 kΩ
-10 V to +10 VYes; 16 bit incl. sign
— Input resistance (-10 V to +10 V)120 kΩ
-5 V to +5 VYes; 16 bit incl. sign
— Input resistance (-5 V to +5 V)120 kΩ
Input ranges (rated values), currents
0 to 20 mAYes; 15 bit
— Input resistance (0 to 20 mA)100 Ω; + approx. 0.7 V diode forward voltage
4 mA to 20 mAYes; 15 bit
— Input resistance (4 mA to 20 mA)100 Ω; + approx. 0.7 V diode forward voltage
Cable length
shielded, max.1 000 m; 200 m for voltage measurement
Analog value generation for the inputs
Measurement principleintegrating (Sigma-Delta)
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Integration time, parameterizableYes
Interference voltage suppression for interference frequency f1 in Hz16.6 / 50 / 60 Hz
Conversion time (per channel)180 / 60 / 50 ms
Smoothing of measured values
Number of smoothing levels4; None; 4/8/16 times
ParameterizableYes
Connection of signal encoders
for voltage measurementYes
for current measurement as 2-wire transducerYes
— Burden of 2-wire transmitter, max.650 Ω
for current measurement as 4-wire transducerNo
Errors/accuracies
Linearity error (relative to input range), (+/-)0.02 %
Temperature error (relative to input range), (+/-)0.005 %/K
Crosstalk between the inputs, min.50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.05 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)1.3 %
Current, relative to input range, (+/-)1.3 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.3 %
Current, relative to input range, (+/-)0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.70 dB
Common mode voltage, max.10 V
Common mode interference, min.90 dB
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Limit value alarmNo
Diagnoses
Monitoring the supply voltageYes
Wire breakYes; at 4 to 20 mA
short-circuitYes; with 1 to 5 V or 2-wire mode: Short-circuit of the encoder supply to ground or of an input to the encoder supply
Group errorYes
Overflow/UnderflowYes
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED)Yes; green LED
Channel status displayYes; green LED
for channel diagnosticsNo
for module diagnosticsYes; green/red LED
Potential separation channels
between the channelsYes; channel group-specific between 2-wire current input group and voltage input group
between the channels and backplane busYes
between the channels and the power supply of the electronicsYes; only for voltage inputs
Permissible potential difference
between the inputs (UCM)10 V DC
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Suitable for applications according to AMS 2750Yes; Declaration of Conformity, see online support entry 109757262
Suitable for applications according to CQI-9Yes
Ambient temperature during operation
horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.70 °C; = Tmax; > 60 °C max. 1x ±20 mA or 4x ±10 V permissible
vertical installation, min.-40 °C; = Tmin
vertical installation, max.50 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-6Yes; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width15 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.31 g