General information
Product type designationAI 2xU/I 2-/4-wire HF
Firmware versionV1.0
FW update possibleYes
based on6ES7134-6HB00-0CA1
usable BaseUnitsBU type A0, A1
Color code for module-specific color-coded labelCC03
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeYes
Measuring range scalableNo
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
OversamplingNo
MSIYes
CiR - Configuration in RUN
Reparameterization possible in RUNYes
Calibration possible in RUNYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption (rated value)39 mA; without sensor supply
24 V encoder supply
24 VYes
Short-circuit protectionYes
Output current, max.20 mA; max. 50 mA per channel for a duration < 10 s (two-wire)
Additional 24 V encoder supply
Short-circuit protectionYes; channel by channel
Output current, max.100 mA; max. 150 mA for a duration of < 10 s (four-wire)
Power loss
Power loss, typ.0.95 W; without sensor supply
Address space per module
Address space per module, max.4 byte; + 1 byte for QI information
Hardware configuration
Automatic encodingYes
Mechanical coding elementYes
Type of mechanical coding elementType A
Selection of BaseUnit for connection variants
2-wire connectionBU type A0, A1
4-wire connectionBU type A0, A1
Analog inputs
Number of analog inputs2; Differential inputs
For current measurement2
For voltage measurement2
permissible input voltage for voltage input (destruction limit), max.30 V
permissible input current for current input (destruction limit), max.50 mA
Analog input with oversamplingNo
Standardization of measured valuesYes
Input ranges (rated values), voltages
0 to +10 VYes; 15 bit
— Input resistance (0 to 10 V)75 kΩ
1 V to 5 VYes; 15 bit
— Input resistance (1 V to 5 V)75 kΩ
-10 V to +10 VYes; 16 bit incl. sign
— Input resistance (-10 V to +10 V)75 kΩ
-5 V to +5 VYes; 16 bit incl. sign
— Input resistance (-5 V to +5 V)75 kΩ
Input ranges (rated values), currents
0 to 20 mAYes; 15 bit
— Input resistance (0 to 20 mA)130 Ω
-20 mA to +20 mAYes; 16 bit incl. sign
— Input resistance (-20 mA to +20 mA)130 Ω
4 mA to 20 mAYes; 15 bit
— Input resistance (4 mA to 20 mA)130 Ω
Cable length
shielded, max.1 000 m; 200 m for voltage measurement
Analog value generation for the inputs
Measurement principleSigma Delta
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Integration time, parameterizableYes
Integration time (ms)67.5 / 22.5 / 18.75 / 10 / 5 / 2.5 / 1.25 / 0.625 ms
Basic conversion time, including integration time (ms)68.03 / 22.83 / 19.03 / 10.28 / 5.23 / 2.68 / 1.43 / 0.730 ms
Interference voltage suppression for interference frequency f1 in Hz16.6 / 50 / 60 / 300 / 600 / 1 200 / 2 400 / 4 800
Conversion time (per channel)68.2 / 23 / 19.2 / 10.45 / 5.40 / 2.85 / 1.6 / 0.9 ms
Basic execution time of the module (all channels released)1 ms
Smoothing of measured values
Number of smoothing levels6; none; 2-/4-/8-/16-/32-fold
parameterizableYes
Connection of signal encoders
for voltage measurementYes
for current measurement as 2-wire transducerYes
— Burden of 2-wire transmitter, max.650 Ω
for current measurement as 4-wire transducerYes
Errors/accuracies
Linearity error (relative to input range), (+/-)0.01 %
Temperature error (relative to input range), (+/-)0.003 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.01 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0.2 %
Current, relative to input range, (+/-)0.2 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.05 %; 0.1 % at SFU 4.8 kHz
Current, relative to input range, (+/-)0.05 %; 0.1 % at SFU 4.8 kHz
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Common mode voltage, max.35 V
Common mode interference, min.90 dB
Isochronous mode
Filtering and processing time (TCI), min.800 µs
Bus cycle time (TDP), min.1 ms
Jitter, max.5 µs
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Limit value alarmYes; two upper and two lower limit values in each case
Diagnoses
Monitoring the supply voltageYes
Wire breakYes; Measuring range 4 to 20 mA only
Short-circuitYes; channel-by-channel, at 1 to 5 V or for short-circuit in encoder supply
Group errorYes
Overflow/UnderflowYes
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; green/red DIAG LED
Potential separation channels
between the channelsYes
between the channels and backplane busYes
between the channels and the power supply of the electronicsYes
Isolation
Isolation tested with707 V DC (type test)
Ambient temperature during operation
horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.60 °C; = Tmax; +70 °C with spacing modules (6AG1193-6BN00-7BA0) or configured slots to the left and right of the module including derating of the encoder supply to max. 50 mA per channel
vertical installation, min.-40 °C; = Tmin (incl. condensation/frost); start-up @ -30 °C
vertical installation, max.50 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-6Yes; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width15 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.32 g