General information
product brand nameSIPLUS
product type designationUPS1100
product designationBattery module 7 Ah
type of batterymaintenance-free lead-acid batteries
product versionExtension module/battery module
manufacturer's article number of the basic version used for SIPLUS product versions6EP4134-0GB00-0AY0
electrical data
at -10 °C recommended28 V
at 0 °C recommended28 V
at 10 °C recommended27.8 V
at 20 °C recommended27.3 V
at 30 °C recommended26.8 V
at 40 °C recommended26.6 V
at 50 °C recommended26.3 V
output
battery capacity7 A·h
output current rated value40 A
output current in buffering mode maximum40 A
peak current120 A; for 30 ms
charging current maximum2.1 A
output voltage at DC rated value24 V
interfaces
communication functionYes
protection and monitoring
design of short-circuit protectionBattery fuse 2x 25 A/32 V (solid-state circuitry blade-type fuse + support)
design of the overload protectionValve control
display version for normal operationLED green: Battery OK; LED flashing green: Error or warning; OFF: No communication
safety
operating resource protection classClass III
protection class IPIP20
standards, specifications, approvals
CE markingYes
UKCA markingYes
ambient conditions
ambient conditionFor storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away.
in horizontal mounting position during operation-15 ... +50 °C
during transport-20 ... +50 °C
during storage-20 ... +50 °C
relative temporary capacity loss at 20 °C in a month typical3 %
installation altitude at height above sea level maximum6 000 m
ambient condition relating to ambient temperature - air pressure - installation altitudeIn case of operation at altitudes of 2000 - 6000 m above sea level: Reduction of the ambient temperature by 5 K/1000 m
relative humidity with condensation according to IEC 60068-2-38 maximum100 %; RH incl. condensation/frost (no commissioning if condensation is present), horizontal installation
resistance to biologically active substances conformity according to EN 60721-3-3Yes; Class 3B2 mold, fungal, sponge spores (except fauna); class 3B3 upon request
resistance to chemically active substances conformity according to EN 60721-3-3Yes; Class 3C4 (RH < 75%) incl. salt spray acc. to EN 60068-2-52 (severity level 3)
resistance to mechanically active substances conformity according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust
resistance to biologically active substances conformity according to EN 60721-3-6Yes; Class 6B2 mold, fungal, sponge spores (except fauna)
resistance to chemically active substances conformity according to EN 60721-3-6Yes; Class 6C3 (RH < 75%) incl. salt spray acc. to EN 60068-2-52 (severity level 3)
resistance to mechanically active substances conformity according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust
coating for equipped printed circuit board according to EN 61086Yes; Class 2 for high availability
type of coating protection against pollution according to EN 60664-3Yes; Type 1 protection
type of test of the coating according to MIL-I-46058CYes; Discoloration of the coating during service life possible
product conformity of the coating Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal Coating, Class A
service life
typicalcapacity falls to 80 % of original capacity (according to EUROBAT)
at 20 °C typical4 a
at 30 °C typical2 a
at 40 °C typical1 a
at 50 °C typical0.5 a
noteAlong with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C.
connection method
type of electrical connectionscrew terminal
for UPS module1 screw terminal each for 0.5 ... 16 mm² for + BAT and - BAT
for control circuit and status message1 screw terminal each for 0.14 ... 4 mm²
mechanical data
width × height × depth of the enclosure186 × 186 × 110 mm
installation width × mounting height186 mm × 201 mm
top15 mm
bottom0 mm
left0 mm
right0 mm
fastening methodcan be screwed onto flat surface (keyhole mounting for hooking in to M4 screws)
DIN-rail mountingNo
S7 rail mountingNo
wall mountingYes
net weight6.1 kg
number of cells12
accessories
product component includedAccessories pack with solid-state circuitry fuse 25 A
additional information
other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)