General information
Product type designationDQ 8x24VDC/0,5A ST
FW update possibleNo
based on6ES7132-6BF01-0BA0
usable BaseUnitsBU type A0
Color code for module-specific color-coded labelCC02
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
DQYes
DQ with energy-saving functionNo
PWMNo
OversamplingNo
MSONo
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption, max.35 mA; without load
Output voltage
Rated value (DC)24 V
Power loss
Power loss, typ.1 W
Address space per module
Address space per module, max.1 byte; + 1 byte for QI information
Hardware configuration
Automatic encodingYes
Mechanical coding elementYes
Type of mechanical coding elementType A
Selection of BaseUnit for connection variants
1-wire connectionBU type A0
2-wire connectionBU type A0
3-wire connectionBU type A0 with AUX terminals or potential distributor module
4-wire connectionBU type A0 + Potential distributor module
Digital outputs
Type of digital outputSource output (PNP, current-sourcing)
Number of digital outputs8
Current-sinkingNo
Current-sourcingYes
Digital outputs, parameterizableYes
output type acc. to IEC 61131, type 0.5Yes
Short-circuit protectionYes; Electronic
Response threshold, typ.1 A; 0.7 to 1.3 A
Open-circuit detectionYes
Limitation of inductive shutdown voltage toTyp. L+ (-50 V)
Controlling a digital inputYes
Switching capacity of the outputs
with resistive load, max.0.5 A
with inductive load, max.0.5 A
on lamp load, max.5 W
Load resistance range
lower limit48 Ω
upper limit12 kΩ
Output current
for signal "1" rated value0.5 A
for signal "1" permissible range, max.0.5 A
for signal "0" residual current, max.0.1 mA
Output delay with resistive load
"0" to "1", max.50 µs; at rated load
"1" to "0", max.100 µs; at rated load
Parallel switching of two outputs
for upratingNo
for redundant control of a loadYes
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.0.1 Hz; higher frequencies are possible, see Equipment Manual "Maximum permitted switching frequency of inductive loads"
on lamp load, max.10 Hz
Total current of the outputs
Current per channel, max.0.5 A
Current per module, max.4 A
horizontal installation
— up to 60 °C, max.4 A
vertical installation
— up to 50 °C, max.4 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Interrupts/diagnostics/status information
Diagnostics functionYes
Substitute values connectableYes
Alarms
Diagnostic alarmYes
Diagnoses
Monitoring the supply voltageYes
Wire breakYes; module-wise
Short-circuit to groundYes; module-wise
Short-circuit to L+Yes; module-wise
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Channel status displayYes; green LED
for channel diagnosticsNo
for module diagnosticsYes; green/red DIAG LED
Potential separation channels
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+No
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functionsNo
Suitable for safety-related tripping of standard modulesNo
Ecological footprint
environmental product declarationYes
Global warming potential
— global warming potential, (total) [CO2 eq]20.4 kg
— global warming potential, (during production) [CO2 eq]3.16 kg
— global warming potential, (during operation) [CO2 eq]17.5 kg
— global warming potential, (after end of life cycle) [CO2 eq]-0.221 kg
Ambient temperature during operation
horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.70 °C; = Tmax; > +60 °C max. total current 1.0 A
vertical installation, min.-40 °C; = Tmin
vertical installation, max.50 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; incl. condensation / frost permitted (no commissioning under condensation conditions)
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-6Yes; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width15 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.30 g