General information
Product type designationDI 8xNAMUR HF
FW update possibleYes
based on6ES7131-6TF00-0CA0
usable BaseUnitsBU type A0
Color code for module-specific color-coded labelCC01
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
suitable for operation on PROFINET R1 IMsYes
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
DIYes
CounterYes
OversamplingNo
MSINo
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption, max.70 mA
Encoder supply
Number of outputs8
Short-circuit protectionYes
24 V encoder supply
24 VNo
Short-circuit protectionNo
NAMUR encoder supply
8.2 VYes
Short-circuit protectionYes
Output current per channel, max.8 mA
Output current per module, max.64 mA
Power loss
Power loss, typ.1.5 W
Address space per module
Address space per module, max.1 byte
Inputs42 byte; 1 byte + 1 byte for QI information in DI mode; 42 bytes in Counter mode
Outputs20 byte; 0 in DI mode; 20 bytes in Counter mode
Hardware configuration
Automatic encodingYes
Mechanical coding elementYes
Type of mechanical coding elementType A
Submodules
Number of configurable submodules, max.1
Selection of BaseUnit for connection variants
2-wire connectionBU type A0
3-wire connectionBU type A0
Digital inputs
Number of digital inputs8; NAMUR
Digital inputs, parameterizableYes
Sourcing/sinking inputP-reading
Pulse extensionYes; 0.5 s, 1 s, 2 s
Edge evaluationYes; rising edge, falling edge, edge change
Signal change flutterYes; 2 to 32 signal changes
Flutter observation windowYes; 0.5 s, 1 s to 100 s in 1-s steps
Digital input functions, parameterizable
Gate start/stopYes
Freely usable digital inputYes
CounterYes
— Number, max.4; See manual for details
— Counting frequency, max.5 kHz
— Counting width32 bit
— Counting direction up/downYes
Input voltage
Rated value (DC)8.2 V
for 10 k switched contact
— for signal "0", min.0.35 mA
— for signal "0", max.1.2 mA
— for signal "1", min.2.1 mA
— for signal "1", max.7 mA
for unswitched contact
— for signal "0", max. (permissible quiescent current)0.5 mA
— for signal "1", typ.8 mA
for NAMUR encoders
— for signal "0", min.0.35 mA
— for signal "0", max.1.2 mA
— for signal "1", min.2.1 mA
— for signal "1", max.7 mA
Input delay (for rated value of input voltage)
tolerated changeover time for changeover contacts300 ms
for standard inputs
— parameterizableNo
for NAMUR inputs
— at "0" to "1", max.20 ms; See manual for details
— at "1" to "0", max.20 ms; See manual for details
Cable length
shielded, max.200 m; 50 m for Counter mode
Connectable encoders
NAMUR encoder/changeover contact according to EN 60947Yes
Single contact / changeover contact unconnectedYes
Single contact / changeover contact connected with 10 kΩYes
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes; channel by channel
Hardware interruptYes; Parameterizable, channels 0 to 7
Diagnoses
Diagnostic information readableYes
Monitoring the supply voltageYes
— parameterizableYes
Monitoring of encoder power supplyNo
Wire breakYes; channel by channel
Short-circuitYes; channel by channel
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; green/red DIAG LED
Potential separation channels
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+Yes
between the channels and the power supply of the electronicsYes
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functionsNo
Ambient temperature during operation
horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C
horizontal installation, max.70 °C; = Tmax; > +60 °C number of simultaneously controllable inputs max. 4 (no adjacent points)
vertical installation, min.-40 °C; = Tmin
vertical installation, max.50 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-6Yes; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width15 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.32 g