General information
Product type designationDI 4x120...230VAC ST
FW update possibleNo
based on6ES7131-6FD01-0BB1
usable BaseUnitsBU type B1
Color code for module-specific color-coded labelCC41
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
suitable for operation on PROFINET R1 IMsYes
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
DIYes
CounterNo
OversamplingNo
MSINo
Supply voltage
Rated value (AC)230 V
permissible range, upper limit (AC)264 V
Reverse polarity protectionNo
Input current
Current consumption (rated value)10 mA
Encoder supply
Number of outputs4
Short-circuit protectionNo; when using BU type B1, a fuse with 10 A tripping current must be provided
Output current
up to 60 °C, max.10 A
Power loss
Power loss, typ.1 W; Active power, load voltage 230 V, all inputs connected with 230 V, 50 Hz
Address space per module
Address space per module, max.1 byte; + 1 byte for QI information
Hardware configuration
Automatic encodingYes
Mechanical coding elementYes
Type of mechanical coding elementtype C
Selection of BaseUnit for connection variants
1-wire connectionBU type B1
2-wire connectionBU type B1
3-wire connectionBU type B1
4-wire connectionBU type B1 + potential distributor module
Digital inputs
Number of digital inputs4
Digital inputs, parameterizableYes
Sourcing/sinking inputP-reading
Input characteristic curve in accordance with IEC 61131, type 3Yes
Input voltage
Rated value (AC)230 V
for signal "0"0V AC to 40V AC
for signal "1"74 V AC to 264 V AC
Input current
for signal "1", typ.10.8 mA
for standard inputs
— parameterizableNo
— at "0" to "1", min.1.5 ms
— at "0" to "1", max.4 ms
— at "1" to "0", min.10 ms
— at "1" to "0", max.10 ms
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Connectable encoders
2-wire sensorYes
Alarms
Diagnostic alarmNo
Maintenance interruptNo
Hardware interruptNo
Diagnoses
Monitoring the supply voltageNo
Wire breakNo
Short-circuitNo
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Channel status displayYes; green LED
for channel diagnosticsNo
for module diagnosticsYes; green/red DIAG LED
Potential separation channels
between the channelsNo
between the channels and backplane busYes
between the channels and the power supply of the electronicsNo
Isolation
Isolation tested with2 545 V DC/2 s (routine test)
Standards, approvals, certificates
Suitable for safety functionsNo
Ambient temperature during operation
horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.70 °C; = Tmax
vertical installation, min.-40 °C; = Tmin
vertical installation, max.50 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; incl. condensation / frost permitted (no commissioning under condensation conditions)
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-6Yes; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width20 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.36 g