General information
based on6ED1055-1MA00-0BA2
Installation type/mounting
Mountingon 35 mm DIN rail, 2 spacing units wide
Supply voltage
12 V DCYes; 10.8 V DC to 28.8 V DC
24 V DCYes; 10.8 V DC to 28.8 V DC
Input current
Current consumption, typ.30 mA
Analog inputs
Number of analog inputs2
Input ranges
VoltageYes
CurrentYes
Resistance thermometerNo
Input ranges (rated values), voltages
0 to +10 VYes
Input ranges (rated values), currents
0 to 20 mAYes; 0 mA or 4 mA to 20 mA
Input ranges (rated values), resistance thermometer
Pt 100No
Emission of radio interference acc. to EN 55 011
Limit class B, for use in residential areasYes
Degree and class of protection
IP degree of protectionIP20
Ecological footprint
environmental product declarationYes
Global warming potential
— global warming potential, (total) [CO2 eq]16.5 kg
— global warming potential, (during production) [CO2 eq]3.22 kg
— global warming potential, (during operation) [CO2 eq]13.4 kg
— global warming potential, (after end of life cycle) [CO2 eq]-0.124 kg
Ambient temperature during operation
min.-40 °C; = Tmin; Startup @ -25 °C
max.70 °C; = Tmax
At cold restart, min.-25 °C; incl. condensation / frost permitted (no commissioning under condensation conditions)
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width35.5 mm
Height90 mm
Depth58 mm