product brand nameSIRIUS
product designationNetwork monitoring relay with digital setting
design of the productautomatic correction of direction of rotation in case of wrong phase sequence, monitoring of phase failure, phase asymmetry, N conductor (adjustable), frequency, undervoltage and overvoltage for Safety applications
product type designation3UG5
General technical data
product functionline monitoring
display version LEDNo
design of the displayLCD
power loss [W] maximum2 W
power loss [V∙A] maximum5.1 V·A
with degree of pollution 2 rated value690 V
with degree of pollution 3 rated value690 V
degree of pollution3
for monitoringAC
of the operating voltage for actuationAC/DC
surge voltage resistance rated value6 kV
shock resistance according to IEC 60068-2-27sinusoidal half-wave 15 g / 11 ms
vibration resistance according to IEC 60068-2-610 ... 55 Hz: 0.35 mm
switching behaviormonostable
mechanical service life (operating cycles) typical10 000 000
electrical endurance (operating cycles) at AC-15 at 230 V typical100 000
thermal current of the switching element with contacts maximum5 A
adjustable OFF-delay time0 ... 30 s
reference code according to IEC 81346-2K
relative repeat accuracy0 %
Substance Prohibitance (day/month/year)06/01/2023
SVHC substance nameLead CAS-No. 7439-92-1 Lead monoxide (lead oxide) CAS-No. 1317-36-8 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one CAS-No. 71868-10-5 Melamine CAS-No. 108-78-1 6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol CAS-No. 119-47-1
Net Weight0.154 kg
Product Function
undervoltage detectionYes
overvoltage detectionYes
phase sequence recognitionYes
phase failure detectionYes
asymmetry detectionYes
overcurrent detection 1 phaseNo
overvoltage detection 3 phaseYes
undercurrent detection 1 phaseNo
undervoltage detection 3 phasesYes
voltage window recognition 3 phaseYes
adjustable open/closed-circuit current principleYes
auto-RESETYes
neutral conductor monitoring adjustableYes
suitability for use safety-related circuitsYes
Control circuit/ Control
type of voltage of the control supply voltageAC
at 50 Hz200 ... 690 V
at 60 Hz200 ... 690 V
at 50 Hz120 ... 400 V
at 60 Hz120 ... 400 V
initial value0.85
full-scale value1.1
initial value0.85
full-scale value1.1
Supply voltage
supply voltage frequency rated value70 ... 15 Hz
Interfaces
design of the interface bluetoothNo
Measuring circuit
measurable voltage 1 at AC160 ... 760 V
measurable voltage 2 at AC90 ... 440 V
adjustable operating delay time initial value0 s
when starting0.1 ... 999.9 s
with lower or upper limit violation0.1 ... 999.9 s
buffering time in the event of power failure minimum20 ms
response time maximum500 ms
accuracy of digital display+/-1 digit
relative temperature-related measurement deviation1 %
Precision
relative metering precision3 %
temperature drift per °C0 %/°C
Short-circuit protection
for short-circuit protection of the NO contacts of the relay outputs requiredgL/gG: 6 A or MCB type C: 1 A
for short circuit protection of the NC contacts of the relay outputs requiredgL/gG: 6 A or MCB type C: 1 A
Communication/ Protocol
protocol is supported IO-Link protocolNo
type of voltage supply via input/output link masterNo
Auxiliary circuit
material of switching contactsAgSnO2
number of NC contacts delayed switching0
number of NO contacts delayed switching0
for auxiliary contacts2
delayed switching2
operating frequency with 3RT2 contactor maximum5 000 1/h
contact reliability of auxiliary contactsone incorrect switching operation of 100 million switching operations (17 V, 5 mA)
contact rating of auxiliary contacts according to ULR300 / B300
Main circuit
number of poles for main current circuit4
at 250 V at 50/60 Hz3 A
at 24 V1 A
at 110 V0.2 A
at 125 V0 A
at 230 V0.1 A
at 250 V0 A
operational current at 17 V minimum5 mA
continuous current of the DIAZED fuse link of the output relay6 A
Electromagnetic compatibility
EMC emitted interference according to IEC 60947-1class A
due to burst according to IEC 61000-4-42 kV (power ports), 2 kV (signal ports)
due to conductor-earth surge according to IEC 61000-4-52 kV
due to conductor-conductor surge according to IEC 61000-4-51 kV
field-based interference according to IEC 61000-4-310 V/m
electrostatic discharge according to IEC 61000-4-26 kV contact discharge / 8 kV air discharge
Galvanic isolation
design of the electrical isolationgalvanic isolation
between input and outputYes
between the outputsYes
between the voltage supply and other circuitsYes
Safety related data
product function suitable for safety functionYes
safe stateoff
function test interval maximum1 a
IEC 62061
Safety Integrity Level (SIL) according to IEC 62061SIL 1
PFHD with high demand rate according to IEC 620617.6E-7 1/h
ISO 13849
performance level (PL) according to ISO 13849-1PL c
category according to ISO 13849-12
IEC 61508
Safety Integrity Level (SIL) according to IEC 61508SIL 1
safety device type according to IEC 61508-2Type B
PFHD with high demand rate according to IEC 615087.6E-7 1/h
PFDavg with low demand rate according to IEC 615080.0012
Safe failure fraction (SFF)90 %
hardware fault tolerance according to IEC 615080
T1 value of service life according to IEC 6150820 a
Electrical Safety
protection class IP on the front according to IEC 60529IP20
Connections/ Terminals
product component removable terminal for main circuitYes
product component removable terminal for auxiliary and control circuitYes
type of electrical connectionscrew terminal
design of terminals with cross-head screwPZ 1
solid1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
finely stranded with core end processing1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
for AWG cables solid1x (20 ... 12), 2x (20 ... 14)
solid0.5 ... 4 mm²
finely stranded with core end processing0.5 ... 4 mm²
solid20 ... 12
stranded20 ... 12
tightening torque with screw-type terminals0.6 ... 0.8 N·m
stripped length10 mm
Installation/ mounting/ dimensions
mounting positionany
fastening methodscrew and snap-on mounting onto 35 mm DIN rail
height100 mm
width22.5 mm
depth90 mm
— forwards0 mm
— backwards0 mm
— upwards0 mm
— downwards0 mm
— at the side0 mm
— forwards0 mm
— backwards0 mm
— upwards0 mm
— at the side0 mm
— downwards0 mm
— forwards0 mm
— backwards0 mm
— upwards0 mm
— downwards0 mm
— at the side0 mm
Ambient conditions
installation altitude at height above sea level maximum2 000 m
during operation-25 ... +60 °C
during storage-40 ... +85 °C
during transport-40 ... +85 °C
relative humidity during operation maximum70 %
Approvals Certificates
global warming potential [CO2 eq] / during manufacturing5.06 kg
global warming potential [CO2 eq] / during sales0.0432 kg
global warming potential [CO2 eq] / during operation12.3 kg
global warming potential [CO2 eq] / after end of life-0.132 kg
global warming potential [CO2 eq] / total17.3 kg