product brand nameSIMOCODE
product designationanalog modules
product type designationAM
General technical data
input for thermistor connectionNo
input for analog temperature sensorsNo
input for ground fault detectionNo
consumed active power0.9 W
surge voltage resistance rated value4 000 V
shock resistance according to IEC 60068-2-2715 g / 11 ms
vibration resistance according to IEC 60068-2-61 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2 g
reference code according to IEC 81346-2B
reference code according to IEC 81346-2:2019B
Substance Prohibitance (day/month/year)05/01/2012
SVHC substance nameLead monoxide (lead oxide) CAS-No. 1317-36-8 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one CAS-No. 71868-10-5 Melamine CAS-No. 108-78-1 6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol CAS-No. 119-47-1
Net Weight0.11 kg
Electromagnetic compatibility
EMC emitted interference according to IEC 60947-1class A
EMC immunity according to IEC 60947-1corresponds to degree of severity 3
due to burst according to IEC 61000-4-41 kV
due to conductor-earth surge according to IEC 61000-4-52 kV
due to conductor-conductor surge according to IEC 61000-4-51 kV
field-based interference according to IEC 61000-4-310 V/m
Inputs/ Outputs
number of inputs2
number of digital inputs0
number of analog inputs2
input current as destruction limit maximum permissible40 mA
input resistance50 Ω
A/D resolution at the analog input12 bit
A/D conversion time at the analog input150 ms
diagnostics function at the analog input open-circuit detectionYes
measuring range of current parameterizable0/4 mA ... 20 mA
relative symmetrical measuring accuracy1 %
relative symmetrical accuracy of output signal1 %
number of outputs1
number of semiconductor outputs0
number of outputs as contact-affected switching element0
number of analog outputs1
output load at analog output maximum500 Ω
D/A conversion time at analog output25 ms
A/D resolution at analog output12 bit
output voltage maximum30 V
type of voltage of the output voltageDC
property of the output short-circuit proofYes
value range of output current parameterizable0/4 mA ... 20 mA
Installation/ mounting/ dimensions
mounting positionany
fastening methodscrew and snap-on mounting
height92 mm
width22.5 mm
depth124 mm
top40 mm
bottom40 mm
left0 mm
right0 mm
Connections/ Terminals
type of electrical connection for auxiliary and control circuitscrew-type terminals
type of connection technology2-wire connection
at inputshield recommended up to 30 m and/or when exiting control cabinet, shield required from 30 m
at outputshield recommended up to 30 m and/or when exiting control cabinet, shield required from 30 m
solid1x (0.5 ... 4.0mm²), 2x (0.5 ... 2.5 mm²)
finely stranded with core end processing1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
for AWG cables solid1x (20 ... 14), 2x (20 ... 16)
for AWG cables stranded1x (20 ... 12), 2x (20 ... 14)
tightening torque with screw-type terminals0.8 ... 1.2 N·m
tightening torque [lbf·in] with screw-type terminals7 ... 10.3 lbf·in
Ambient conditions
1 maximum2 000 m
2 maximum3 000 m; max. +50 °C (no protective separation)
3 maximum4 000 m; max. +40 °C (no protective separation)
during operation-25 ... +60 °C
during storage-40 ... +80 °C
during transport-40 ... +80 °C
during operation according to IEC 607213K6 (no formation of ice, no condensation, relative humidity 10 ... 95%), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
during storage according to IEC 607211K6 (no condensation, relative humidity 10 ... 95%), 1C2 (no salt mist), 1S2 (sand must not get into the devices), 1M4
during transport according to IEC 607212K2, 2C1, 2S1, 2M2
relative humidity during operation5 ... 95 %
Electrical Safety
touch protection against electrical shockfinger-safe
Galvanic isolation
between output and electronicsNo
between inputs and electronicsNo