product designationContactor
product type designation3TC
General technical data
size of contactor2
function module for communicationNo
auxiliary switchYes
insulation voltage rated value800 V
maximum permissible voltage for protective separation between coil and main contacts according to EN 60947-1300 V
at AC7,5 g / 5 ms, 3,4 g / 10 ms
of contactor typical10 000 000
of the contactor with added auxiliary switch block typical10 000 000
reference code according to IEC 81346-2Q
Substance Prohibitance (day/month/year)02/01/2012
SVHC substance nameLead CAS-No. 7439-92-1 6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol CAS-No. 119-47-1
Net Weight0.689 g
Ambient conditions
during operation-25 ... +55 °C
during storage-50 ... +80 °C
relative humidity minimum10 %
relative humidity at 55 °C according to IEC 60068-2-30 maximum95 %
Main circuit
number of poles2
number of poles for main current circuit2
number of NO contacts for main contacts2
number of NC contacts for main contacts0
type of voltageDC
— at 24 V rated value32 A
— at 110 V rated value32 A
— at 220 V rated value32 A
— at 24 V rated value32 A
— at 110 V rated value32 A
— at 220 V rated value32 A
— at 440 V rated value32 A
— at 600 V rated value32 A
— at 750 V rated value32 A
— at 220 V rated value32 A
— at 600 V rated value21 A
— at 750 V rated value7.5 A
— at 24 V rated value32 A
— at 110 V rated value32 A
— at 220 V rated value32 A
— at 24 V rated value32 A
— at 110 V rated value32 A
— at 220 V rated value32 A
— at 440 V rated value29 A
— at 600 V rated value21 A
— at 750 V rated value7.5 A
— at 110 V rated value3.5 kW
— at 220 V rated value7 kW
— at 440 V rated value14 kW
— at 750 V rated value24 kW
— at 110 V rated value2.5 kW
— at 220 V rated value5 kW
— at 440 V rated value9 kW
— at 600 V rated value9 kW
— at 750 V rated value4 kW
at DC-1 maximum1 500 1/h
at DC-3 maximum750 1/h
at DC-5 maximum750 1/h
Control circuit/ Control
type of voltage of the control supply voltageAC
at 50 Hz rated value208 V
at 60 Hz rated value208 V
at 50 Hz0.8 ... 1.1
at 60 Hz0.85 ... 1.1
apparent pick-up power of magnet coil at AC79 V·A
at 50 Hz68 V·A
at 60 Hz95 V·A
inductive power factor with closing power of the coil0.83
at 50 Hz0.86
at 60 Hz0.79
apparent holding power of magnet coil at AC11 V·A
at 50 Hz10 V·A
at 60 Hz12 V·A
inductive power factor with the holding power of the coil0.28
at 50 Hz0.29
at 60 Hz0.3
arcing time20 ... 30 ms
Auxiliary circuit
number of NC contacts for auxiliary contacts2
instantaneous contact2
number of NO contacts for auxiliary contacts2
instantaneous contact2
number of CO contacts for auxiliary contacts0
identification number and letter for switching elements22
operational current at AC-12 maximum10 A
at 230 V rated value5.6 A
at 400 V rated value3.6 A
at 500 V rated value2.5 A
at 24 V rated value10 A
at 48 V rated value10 A
at 60 V rated value10 A
at 110 V rated value3.2 A
at 125 V rated value2.5 A
at 220 V rated value0.9 A
at 600 V rated value0.22 A
at 24 V rated value10 A
at 48 V rated value5 A
at 60 V rated value5 A
at 110 V rated value1.14 A
at 125 V rated value0.98 A
at 220 V rated value0.48 A
at 600 V rated value0.07 A
UL/CSA ratings
contact rating of auxiliary contacts according to ULA600 / P600
Short-circuit protection
— with type of coordination 1 required2 x 3NA3020 (50 A) in series (750 V, 3 kA)
— with type of coordination 2 required2 x 3NA3020 (50 A) in series (750 V, 3 kA)
for short-circuit protection of the auxiliary switch requiredgG: 16 A (500 V, 1 kA)
Installation/ mounting/ dimensions
mounting position+/-22,5° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
fastening method side-by-side mountingYes
fastening methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022
height85 mm
width70 mm
depth104 mm
— forwards15 mm
— backwards0 mm
— upwards10 mm
— downwards10 mm
— at the side10 mm
— forwards30 mm
— backwards0 mm
— upwards10 mm
— at the side10 mm
— downwards10 mm
— forwards30 mm
— backwards0 mm
— upwards10 mm
— downwards10 mm
— at the side10 mm
Connections/ Terminals
type of electrical connectionscrew terminal
for main current circuitscrew-type terminals
for auxiliary and control circuitscrew-type terminals
solid or stranded2x (2,5 ... 10 mm²)
finely stranded with core end processing2x (1.5 ... 4 mm²)
— solid or stranded2x (1 ... 2.5 mm²)
— finely stranded with core end processing2x (0.75 ... 1.5 mm²)
Safety related data
product function mirror contact according to IEC 60947-4-1Yes; One NC contact each must be connected in series for the right and left auxiliary switch block respectively
Electrical Safety
protection class IP on the front according to IEC 60529IP00