product brand nameSIRIUS ACT
product designationLED module
product type designation3SU1
General technical data
diodeYes
lamp transformerNo
light sourceYes
series resistorNo
insulation voltage rated value320 V
degree of pollution3
type of voltage of the operating voltageAC/DC
for actuationAC/DC
surge voltage resistance rated value4 kV
consumed current maximum20 mA
of the enclosureIP30
of the terminalIP20
according to IEC 60068-2-27sinusoidal half-wave 15 g / 11 ms
for railway applications according to EN 61373Category 1, Class B
according to IEC 60068-2-610 ... 500 Hz: 5 g
for railway applications according to EN 61373Category 1, Class B
operating period typical100 000 h
reference code according to IEC 81346-2P
Substance Prohibitance (day/month/year)08/14/2018
SVHC substance nameLead monoxide (lead oxide) CAS-No. 1317-36-8 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one CAS-No. 71868-10-5 Melamine CAS-No. 108-78-1
Net Weight0.01 kg
— at 50 Hz rated value24 V
— at 60 Hz rated value24 V
at DC rated value24 V
Control circuit/ Control
inrush current maximum2 A
Connections/ Terminals
type of electrical connectionscrew terminal
solid with core end processing2x (0.5 ... 0.75 mm²)
solid without core end processing2x (1.0 ... 1.5 mm²)
finely stranded with core end processing2x (0.5 ... 1.5 mm²)
finely stranded without core end processing2x (1,0 ... 1,5 mm²)
for AWG cables2x (18 ... 14)
connectable conductor cross-section finely stranded with core end processing0.5 ... 1.5 mm²
tightening torque with screw-type terminals0.8 ... 0.9 N·m
Lamp
type of light sourceLED
color of the light sourceamber
light intensity450 ... 1 120 mcd
ATEX
ATEXYes; BVS 18 ATEX E 030 (IEC 60079-0:2017-12 Edition 7.0; EN 60079-11:2012; ATEX-product guideline 2014/34/EU)
IECExYes; IECEx BVS 18.0023 (IEC 60079-11:2011-06 Edition 6.0; IEC 60079-0:2017-12 Edition 7.0)
for gas explosion protection for zone 1/2Yes
explosion device group and category according to ATEXII C
Ex-Marking according to ATEXII 2G Ex ib IIC T4 Gb
equipment protection level (EPL) according to ATEXGb
at AC28.8 V
at DC28.8 V
type of protection according to ATEXEx ib
Ambient conditions
during operation-25 ... +70 °C
during storage-40 ... +80 °C
environmental category during operation according to IEC 607213M6, 3S2, 3B2, 3C3, 3K6 (with relative air humidity of 10 ... 95%, no condensation in operation permitted)
Installation/ mounting/ dimensions
of modules and accessoriesFront plate mounting
height33.2 mm
width9.8 mm
depth29.4 mm
Environmental footprint
Environmental Product Declaration(EPD)Yes
global warming potential [CO2 eq] total0.787 kg
global warming potential [CO2 eq] during manufacturing0.566 kg
global warming potential [CO2 eq] during operation0.235 kg
global warming potential [CO2 eq] after end of life-0.015 kg
Approvals Certificates
global warming potential [CO2 eq] / during manufacturing0.566 kg
global warming potential [CO2 eq] / during operation0.235 kg
global warming potential [CO2 eq] / after end of life-0.0145 kg
global warming potential [CO2 eq] / total0.787 kg
Product information
Product familyModules
Life cycle statusActive
Commodity code85369095
Delivery and logistics
Country of originCzech Republic
Standard delivery time5 Day/Days
ReturnableYes
Net weight0.01 Kg
Packaging dimensions (L x W x H)154 x 100 x 30 MM
Standard package quantity1 Piece
Minimum order quantity150
Dangerous goodsNo
Export control regulationsAL : N / ECCN : EAR99
Environment and compliance
RoHS conformitySince: 14-08-18
WEEE category5
REACH informationLead monoxide (lead oxide) CAS-No. 1317-36-8 > 0,1 % (w / w)
Siemens catalog
Product group5452
Catalog IDCC-IC10
Group codeR711
Product classStraightforward, can be reused over the short term