product brand nameSIRIUS ACT
product designationFail-safe interface module for PROFINET
product type designation3SU1
Display
for diagnostic function: Supply voltage monitoring power LEDYes
status Tx/Rx linkYes
General technical data
reverse polarity protectionYes; With polarity change, DI1 ... DI4 may not be connected to (M) pole
diagnostics functionYes
alarmsYes
I&M dataYes; I&M0 ... I&M3
firmware version2.1.4
hardware version1
configuration function with datasetYes
software version with STEP 7 in the TIA Portal requiredIntegrated in TIA Portal Version 14 SP1 or higher (HSP for V13 and V14)
number of units per rack maximum20
number of submodules per station maximum24
power loss [W] typical0.67 W
insulation voltage rated value30 V
degree of pollution3
of the operating voltageDC
of the input voltageDC
surge voltage resistance rated value0.8 kV
maximum100 mA
rated value28 mA
protection class IPIP20, clamping screw tightened
according to IEC 60068-2-27sinusoidal half-wave 15 g / 11 ms
for railway applications according to EN 61373Category 1, Class B
according to IEC 60068-2-610 ... 500 Hz: 5 g
for railway applications according to EN 61373Category 1, Class B
reference code according to IEC 81346-2K
Substance Prohibitance (day/month/year)06/08/2018
SVHC substance nameLead CAS-No. 7439-92-1 Lead monoxide (lead oxide) CAS-No. 1317-36-8 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one CAS-No. 71868-10-5 Melamine CAS-No. 108-78-1
Net Weight120 g
operating voltage rated value minimum20.4 V
I2t value0.008 A²·s
Supply voltage
supply voltage at DC rated value24 V
Communication/ Protocol
PROFINET IO protocolYes
PROFIsafe protocolYes
AutocrossoverYes
AutonegotiationYes
protocol at the 1st interface media redundancy protocolNo
product function at the 1st interface PROFINET IO deviceYes
product function of the PROFINET IO device is supported PROFINET system redundancyNo
prioritized startupNo
isochronous modeNo
supports Shared DeviceNo
supports PROFIenergyNo
IRTNo
MRPNo
MRPDNo
LLDPYes
SNMPYes
TCP/IPYes
GSD version/revision with PROFINET requiredV2.34
transmission mode for Industrial EthernetPROFINET with 100 Mbps full duplex (100BASE-TX)
network load class according to PROFINETI
specification for Security Level 1 test according to PROFINETResilient to network loading
Control circuit/ Control
inrush current maximum16 A
Galvanic isolation
galvanic isolation between PROFINET and all other circuitsYes
Inputs/ Outputs
number of digital inputs4
safety-related0
number of analog inputs1
number of digital outputs1
Connections/ Terminals
type of electrical connectionscrew terminal
solid or stranded0.2 ... 2.5 mm²
finely stranded with core end processing maximum2.5 mm²
solid0.2 ... 2.5 mm²
solid with core end processing0.2 ... 2.5 mm²
finely stranded with core end processing0.25 ... 2.5 mm²
finely stranded without core end processing0.2 ... 2.5 mm²
AWG number as coded connectable conductor cross section30 ... 12
tightening torque with screw-type terminals0.5 ... 0.6 N·m
Safety related data
product function suitable for safety functionYes
safe stateProcess value within PROFISafe telegram is set to zero
service life maximum20 a
test wear-related service life necessaryNo
function test interval maximum1 mo
IEC 62061
Safety Integrity Level (SIL) according to IEC 62061SIL 3
PFHD with high demand rate according to IEC 620616E-10 1/h
ISO 13849
performance level (PL) according to ISO 13849-1PL e
category according to ISO 13849-14
device type according to ISO 13849-11
IEC 61508
Safety Integrity Level (SIL) according to IEC 61508SIL 3
safety device type according to IEC 61508-2Type B
PFHD with high demand rate according to IEC 615086E-10 1/h
PFDavg with low demand rate according to IEC 615082.426E-6
Safe failure fraction (SFF)99.6 %
hardware fault tolerance according to IEC 615081
according to IEC 615081 a
of service life according to IEC 6150820 a
Interfaces
Ethernet interfaceYes; for Ethernet services
Fast Ethernet interfaceYes; PROFINET with 100 Mbps
integrated switchNo
RJ45 (Ethernet)Yes
number of ports at the 1st interface1
number of interfaces according to PROFINET1
Ambient conditions
during operation-25 ... +60 °C
during storage-40 ... +80 °C
environmental category during operation according to IEC 607213M6, 3S2, 3B2, 3K6 (with relative air humidity of 10 ... 95%, no condensation in operation permitted)
explosion protection marking for intrinsic safety of related equipment EEx iaNo
explosion protection marking for intrinsic safety of related equipment EEx ibNo
Installation/ mounting/ dimensions
fastening method of modules and accessoriesFront plate mounting
height80.1 mm
width40 mm
depth72.1 mm
Environmental footprint
Environmental Product Declaration(EPD)Yes
global warming potential [CO2 eq] total0.787 kg
global warming potential [CO2 eq] during manufacturing0.566 kg
global warming potential [CO2 eq] during operation0.235 kg
global warming potential [CO2 eq] after end of life-0.015 kg
Approvals Certificates
global warming potential [CO2 eq] / during manufacturing0.566 kg
global warming potential [CO2 eq] / during operation0.235 kg
global warming potential [CO2 eq] / after end of life-0.0145 kg
global warming potential [CO2 eq] / total0.787 kg
Product information
Product familyModules
Life cycle statusActive
Commodity code85371098
Delivery and logistics
Country of originCzech Republic
Standard delivery time10 Day/Days
ReturnableYes
Net weight0.12 Kg
Packaging dimensions (L x W x H)115 x 100 x 55 MM
Standard package quantity1 Piece
Minimum order quantity1
Dangerous goodsNo
Export control regulationsAL : N / ECCN : EAR99
Environment and compliance
RoHS conformitySince: 08-06-18
WEEE category5
REACH informationLead CAS-No. 7439-92-1 > 0,1 % (w / w)
Siemens catalog
Product group5453
Catalog IDCC-IC10
Group codeR711
Product classStraightforward, can be reused over the short term