product brand nameSIRIUS
product designationcontactor
product type designation3RT25
General technical data
size of contactorS00
function module for communicationNo
auxiliary switchYes
at AC in hot operating state per pole0.5 W
without load current share typical1.5 W
type of calculation of power loss current-dependentquadratic
of main circuit with degree of pollution 3 rated value690 V
of auxiliary circuit with degree of pollution 3 rated value690 V
of main circuit rated value6 kV
of auxiliary circuit rated value6 kV
maximum permissible voltage for protective separation between coil and main contacts according to EN 60947-1400 V
at AC7,3 g / 5 ms, 4,7 g / 10 ms
at AC11,4 g / 5 ms, 7,3 g / 10 ms
of contactor typical30 000 000
of the contactor with added electronically optimized auxiliary switch block typical5 000 000
of the contactor with added auxiliary switch block typical10 000 000
reference code according to IEC 81346-2Q
Substance Prohibitance (day/month/year)10/01/2009
Net Weight0.239 kg
Ambient conditions
installation altitude at height above sea level maximum2 000 m
during operation-25 ... +60 °C
during storage-55 ... +80 °C
relative humidity minimum10 %
relative humidity at 55 °C according to IEC 60068-2-30 maximum95 %
Main circuit
number of poles for main current circuit4
number of NO contacts for main contacts2
number of NC contacts for main contacts2
— at ambient temperature 40 °C rated value22 A
— at ambient temperature 60 °C rated value20 A
— per NO contact rated value12 A
— per NC contact rated value9 A
minimum cross-section in main circuit at maximum AC-1 rated value4 mm²
— at 24 V rated value20 A
— at 110 V rated value2.1 A
— at 220 V rated value0.8 A
— at 440 V rated value0.6 A
— at 24 V rated value20 A
— at 110 V rated value12 A
— at 220 V rated value1.6 A
— at 440 V rated value0.8 A
— at 24 V per NC contact rated value20 A
— at 24 V per NO contact rated value20 A
— at 110 V per NC contact rated value0.075 A
— at 110 V per NO contact rated value0.15 A
— at 220 V per NC contact rated value0.375 A
— at 220 V per NO contact rated value0.75 A
— at 24 V per NC contact rated value20 A
— at 24 V per NO contact rated value20 A
— at 110 V per NC contact rated value0.175 A
— at 110 V per NO contact rated value0.35 A
at 230 V per NC contact rated value2.2 kW
at 230 V per NO contact rated value3 kW
at 400 V per NC contact rated value4 kW
at 400 V per NO contact rated value5.5 kW
limited to 1 s switching at zero current maximum125 A; Use minimum cross-section acc. to AC-1 rated value
limited to 5 s switching at zero current maximum123 A; Use minimum cross-section acc. to AC-1 rated value
limited to 10 s switching at zero current maximum96 A; Use minimum cross-section acc. to AC-1 rated value
limited to 30 s switching at zero current maximum74 A; Use minimum cross-section acc. to AC-1 rated value
limited to 60 s switching at zero current maximum61 A; Use minimum cross-section acc. to AC-1 rated value
power loss [W] at AC-3 at 400 V for rated value of the operational current per conductor0.5 W
power loss [W] at AC-3e at 400 V for rated value of the operational current per conductor0.5 W
at AC10 000 1/h
at DC10 000 1/h
at AC-1 maximum1 000 1/h
Control circuit/ Control
type of voltage of the control supply voltageAC
at 50 Hz rated value230 V
at 60 Hz rated value230 V
at 50 Hz0.8 ... 1.1
at 60 Hz0.85 ... 1.1
apparent pick-up power of magnet coil at AC37 V·A
at 50 Hz37 V·A
at 60 Hz33 V·A
inductive power factor with closing power of the coil0.8
at 50 Hz0.8
at 60 Hz0.75
apparent holding power of magnet coil at AC5.7 V·A
at 50 Hz5.7 V·A
at 60 Hz4.4 V·A
inductive power factor with the holding power of the coil0.25
at 50 Hz0.25
at 60 Hz0.25
at AC9 ... 35 ms
at AC4 ... 15 ms
arcing time10 ... 15 ms
at AC at 230 V maximum permissible0.004 A
Auxiliary circuit
number of NC contacts for auxiliary contacts instantaneous contact0
number of NO contacts for auxiliary contacts instantaneous contact0
operational current at AC-12 maximum10 A
at 230 V rated value10 A
at 400 V rated value3 A
at 48 V rated value6 A
at 60 V rated value6 A
at 110 V rated value3 A
at 125 V rated value2 A
at 220 V rated value1 A
at 600 V rated value0.15 A
at 24 V rated value10 A
at 48 V rated value2 A
at 60 V rated value2 A
at 110 V rated value1 A
at 220 V rated value0.3 A
at 600 V rated value0.1 A
contact reliability of auxiliary contacts1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings
for single-phase AC motor at 230 V rated value2 hp
for 3-phase AC motor at 460/480 V rated value5 hp
contact rating of auxiliary contacts according to ULA600 / Q600
Short-circuit protection
— with type of coordination 1 requiredgG: 35 A (690 V, 100 kA)
— with type of coordination 2 requiredgG: 20 A (690 V, 100 kA)
Installation/ mounting/ dimensions
mounting position+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
fastening method side-by-side mountingYes
fastening methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022
height70 mm
width45 mm
depth73 mm
— forwards0 mm
— backwards0 mm
— upwards0 mm
— downwards0 mm
— at the side0 mm
— forwards0 mm
— backwards0 mm
— upwards0 mm
— at the side6 mm
— downwards0 mm
— forwards0 mm
— backwards0 mm
— upwards0 mm
— downwards0 mm
— at the side6 mm
Connections/ Terminals
for main current circuitspring-loaded terminals
for auxiliary and control circuitspring-loaded terminals
at contactor for auxiliary contactsSpring-type terminals
of magnet coilSpring-loaded terminal
— solid2x (0.5 ... 4 mm²)
— solid or stranded2x (0,5 ... 4 mm²)
— finely stranded with core end processing2x (0.5 ... 2.5 mm²)
— finely stranded without core end processing2x (0.5 ... 2.5 mm²)
for AWG cables for main contacts2x (20 ... 12)
— solid2x (0.5 ... 4 mm²)
— solid or stranded2x (0,5 ... 4 mm²)
— finely stranded with core end processing2x (0.5 ... 2.5 mm²)
— finely stranded without core end processing2x (0.5 ... 2.5 mm²)
for AWG cables for auxiliary contacts2x (20 ... 12)
AWG number as coded connectable conductor cross section for main contacts20 ... 12
AWG number as coded connectable conductor cross section for auxiliary contacts20 ... 12
Safety related data
mirror contact according to IEC 60947-4-1Yes; with 3RH29
positively driven operation according to IEC 60947-5-1No
Electrical Safety
protection class IP on the front according to IEC 60529IP20
touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front