product brand nameSIRIUS
product designationPower contactor
product type designation3RT1
General technical data
size of contactorS10
function module for communicationNo
auxiliary switchYes
at AC in hot operating state66 W
at AC in hot operating state per pole22 W
without load current share typical7.4 W
type of calculation of power loss current-dependentquadratic
of main circuit with degree of pollution 3 rated value1 000 V
of auxiliary circuit with degree of pollution 3 rated value500 V
of main circuit rated value8 kV
of auxiliary circuit rated value6 kV
maximum permissible voltage for protective separation between coil and main contacts according to EN 60947-1690 V
at AC8,5 g / 5 ms, 4,2 g / 10 ms
at DC8,5 g / 5 ms, 4,2 g / 10 ms
at AC13,4 g / 5 ms, 6,5 g / 10 ms
at DC13,4 g / 5 ms, 6,5 g / 10 ms
of contactor typical10 000 000
of the contactor with added electronically optimized auxiliary switch block typical5 000 000
of the contactor with added auxiliary switch block typical10 000 000
reference code according to IEC 81346-2Q
Substance Prohibitance (day/month/year)05/01/2012
SVHC substance nameLead CAS-No. 7439-92-1
Net Weight6.172 kg
Ambient conditions
installation altitude at height above sea level maximum2 000 m
during operation-25 ... +60 °C
during storage-55 ... +80 °C
relative humidity minimum10 %
relative humidity at 55 °C according to IEC 60068-2-30 maximum95 %
Main circuit
number of poles for main current circuit3
number of NO contacts for main contacts3
number of NC contacts for main contacts0
at AC-3 rated value maximum1 000 V
at AC-3e rated value maximum1 000 V
at AC-1 at 400 V at ambient temperature 40 °C rated value330 A
— up to 690 V at ambient temperature 40 °C rated value330 A
— up to 690 V at ambient temperature 60 °C rated value300 A
— up to 1000 V at ambient temperature 40 °C rated value150 A
— up to 1000 V at ambient temperature 60 °C rated value150 A
— at 400 V rated value300 A
— at 500 V rated value300 A
— at 690 V rated value280 A
— at 1000 V rated value95 A
— at 400 V rated value300 A
— at 500 V rated value300 A
— at 690 V rated value280 A
— at 1000 V rated value95 A
at AC-4 at 400 V rated value280 A
at AC-5a up to 690 V rated value290 A
at AC-5b up to 400 V rated value249 A
— up to 230 V for current peak value n=20 rated value292 A
— up to 400 V for current peak value n=20 rated value292 A
— up to 500 V for current peak value n=20 rated value292 A
— up to 690 V for current peak value n=20 rated value280 A
— up to 1000 V for current peak value n=20 rated value95 A
— up to 230 V for current peak value n=30 rated value195 A
— up to 400 V for current peak value n=30 rated value195 A
— up to 500 V for current peak value n=30 rated value195 A
— up to 690 V for current peak value n=30 rated value195 A
— up to 1000 V for current peak value n=30 rated value95 A
minimum cross-section in main circuit at maximum AC-1 rated value185 mm²
at 400 V rated value125 A
at 690 V rated value115 A
— at 24 V rated value300 A
— at 60 V rated value300 A
— at 110 V rated value33 A
— at 220 V rated value3.8 A
— at 440 V rated value0.9 A
— at 600 V rated value0.6 A
— at 24 V rated value300 A
— at 60 V rated value300 A
— at 110 V rated value300 A
— at 220 V rated value300 A
— at 440 V rated value4 A
— at 600 V rated value2 A
— at 24 V rated value300 A
— at 60 V rated value300 A
— at 110 V rated value300 A
— at 220 V rated value300 A
— at 440 V rated value11 A
— at 600 V rated value5.2 A
— at 24 V rated value300 A
— at 60 V rated value11 A
— at 220 V rated value0.6 A
— at 440 V rated value0.18 A
— at 600 V rated value0.125 A
— at 24 V rated value300 A
— at 60 V rated value300 A
— at 110 V rated value300 A
— at 220 V rated value2.5 A
— at 440 V rated value0.65 A
— at 600 V rated value0.37 A
— at 24 V rated value300 A
— at 60 V rated value300 A
— at 110 V rated value300 A
— at 220 V rated value300 A
— at 440 V rated value1.4 A
— at 600 V rated value0.75 A
— at 230 V rated value90 kW
— at 400 V rated value160 kW
— at 500 V rated value200 kW
— at 690 V rated value250 kW
— at 1000 V rated value132 kW
— at 230 V rated value90 kW
— at 400 V rated value160 kW
— at 500 V rated value200 kW
— at 690 V rated value250 kW
— at 1000 V rated value132 kW
at 400 V rated value71 kW
at 690 V rated value112 kW
up to 230 V for current peak value n=20 rated value110 kVA
up to 400 V for current peak value n=20 rated value200 kVA
up to 500 V for current peak value n=20 rated value250 kVA
up to 690 V for current peak value n=20 rated value330 kVA
up to 1000 V for current peak value n=20 rated value160 kVA
up to 230 V for current peak value n=30 rated value70 kVA
up to 400 V for current peak value n=30 rated value130 kVA
up to 500 V for current peak value n=30 rated value160 kVA
up to 690 V for current peak value n=30 rated value230 kVA
up to 1000 V for current peak value n=30 rated value160 kVA
limited to 1 s switching at zero current maximum5 524 A; Use minimum cross-section acc. to AC-1 rated value
limited to 5 s switching at zero current maximum4 579 A; Use minimum cross-section acc. to AC-1 rated value
limited to 10 s switching at zero current maximum3 153 A; Use minimum cross-section acc. to AC-1 rated value
limited to 30 s switching at zero current maximum1 883 A; Use minimum cross-section acc. to AC-1 rated value
limited to 60 s switching at zero current maximum1 445 A; Use minimum cross-section acc. to AC-1 rated value
at AC2 000 1/h
at DC2 000 1/h
at AC-1 maximum750 1/h
at AC-2 maximum250 1/h
at AC-3 maximum500 1/h
— maximum500 1/h
at AC-4 maximum130 1/h
Control circuit/ Control
type of voltage of the control supply voltageAC/DC
at 50 Hz rated value220 ... 240 V
at 60 Hz rated value220 ... 240 V
control supply voltage at DC rated value220 ... 240 V
initial value0.8
full-scale value1.1
at 50 Hz0.8 ... 1.1
at 60 Hz0.8 ... 1.1
design of the surge suppressorwith varistor
— at 50 Hz490 V·A
— at 60 Hz490 V·A
— at 60 Hz590 V·A
— at 50 Hz590 V·A
at 50 Hz590 V·A
at 60 Hz590 V·A
at 50 Hz0.9
at 60 Hz0.9
at minimum rated control supply voltage at DC6.1 V·A
at maximum rated control supply voltage at DC7.4 V·A
— at 50 Hz5.6 V·A
— at 60 Hz5.6 V·A
— at 50 Hz6.7 V·A
— at 60 Hz6.7 V·A
at 50 Hz0.9
at 60 Hz0.9
closing power of magnet coil at DC650 W
holding power of magnet coil at DC7.4 W
at AC30 ... 95 ms
at DC30 ... 95 ms
at AC40 ... 80 ms
at DC40 ... 80 ms
arcing time10 ... 15 ms
control version of the switch operating mechanismStandard A1 - A2
Auxiliary circuit
number of NC contacts for auxiliary contacts instantaneous contact2
number of NO contacts for auxiliary contacts instantaneous contact2
operational current at AC-12 maximum10 A
at 230 V rated value6 A
at 400 V rated value3 A
at 500 V rated value2 A
at 690 V rated value1 A
at 24 V rated value10 A
at 48 V rated value6 A
at 60 V rated value6 A
at 110 V rated value3 A
at 125 V rated value2 A
at 220 V rated value1 A
at 600 V rated value0.15 A
at 24 V rated value10 A
at 48 V rated value2 A
at 60 V rated value2 A
at 110 V rated value1 A
at 125 V rated value0.9 A
at 220 V rated value0.3 A
at 600 V rated value0.1 A
contact reliability of auxiliary contacts1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings
at 480 V rated value302 A
at 600 V rated value289 A
— at 200/208 V rated value100 hp
— at 220/230 V rated value125 hp
— at 460/480 V rated value250 hp
— at 575/600 V rated value300 hp
contact rating of auxiliary contacts according to ULA600 / Q600
Short-circuit protection
design of the miniature circuit breaker for short-circuit protection of the auxiliary circuit up to 230 VC characteristic: 10 A; 0.4 kA
— with type of coordination 1 requiredgG: 500 A (690 V, 100 kA)
— with type of coordination 2 requiredgG: 400 A (690 V, 100 kA), aM: 315 A (690 V, 50 kA), BS88: 400 A (415 V, 50 kA)
for short-circuit protection of the auxiliary switch requiredgG: 10 A (500 V, 1 kA)
Installation/ mounting/ dimensions
mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
fastening method side-by-side mountingYes
fastening methodscrew fixing
height210 mm
width145 mm
depth202 mm
— forwards20 mm
— upwards10 mm
— downwards10 mm
— at the side0 mm
— forwards20 mm
— upwards10 mm
— at the side10 mm
— downwards10 mm
— forwards20 mm
— upwards10 mm
— downwards10 mm
— at the side10 mm
Connections/ Terminals
for main current circuitConnection bar
for auxiliary and control circuitspring-loaded terminals
at contactor for auxiliary contactsSpring-type terminals
of magnet coilSpring-loaded terminal
width of connection bar25 mm
thickness of connection bar6 mm
diameter of holes11 mm
number of holes1
for AWG cables for main contacts2/0 ... 500 kcmil
stranded70 ... 240 mm²
solid or stranded0.25 ... 2.5 mm²
finely stranded with core end processing0.25 ... 1.5 mm²
finely stranded without core end processing0.25 ... 2.5 mm²
— solid2x (0.25 ... 2.5 mm²)
— solid or stranded2x (0,25 ... 2,5 mm²)
— finely stranded with core end processing2x (0.25 ... 1.5 mm²)
— finely stranded without core end processing2x (0.25 ... 2.5 mm²)
for AWG cables for auxiliary contacts2x (24 ... 14)
AWG number as coded connectable conductor cross section for auxiliary contacts24 ... 14
Safety related data
mirror contact according to IEC 60947-4-1Yes
positively driven operation according to IEC 60947-5-1No
suitable for safety functionYes
suitability for use safety-related switching OFFYes
service life maximum20 a
test wear-related service life necessaryYes
with low demand rate according to SN 3192040 %
with high demand rate according to SN 3192073 %
B10 value with high demand rate according to SN 319201 000 000
failure rate [FIT] with low demand rate according to SN 31920100 FIT
ISO 13849
device type according to ISO 13849-13
overdimensioning according to ISO 13849-2 necessaryYes
IEC 61508
safety device type according to IEC 61508-2Type A
Electrical Safety
protection class IP on the front according to IEC 60529IP00; IP20 with box terminal/cover
touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front with box terminal/cover
Approvals Certificates
global warming potential [CO2 eq] / during manufacturing31.5 kg
global warming potential [CO2 eq] / during sales2.6 kg
global warming potential [CO2 eq] / during operation521 kg
global warming potential [CO2 eq] / after end of life-7.22 kg
global warming potential [CO2 eq] / total548 kg