product brand nameSIRIUS
product designationsolid-state overload relay
product type designation3RB3
General technical data
size of overload relayS3
size of contactor can be combined company-specificS3
power loss [W] for rated value of the current at AC in hot operating state0.9 W
per pole0.3 W
type of calculation of power loss current-dependentquadratic
insulation voltage with degree of pollution 3 at AC rated value1 000 V
surge voltage resistance rated value8 kV
in networks with ungrounded star point between auxiliary and auxiliary circuit300 V
in networks with grounded star point between auxiliary and auxiliary circuit300 V
in networks with ungrounded star point between main and auxiliary circuit600 V
in networks with grounded star point between main and auxiliary circuit690 V
shock resistance8 g / 11 ms
according to IEC 60068-2-2715 g / 11 ms; Signaling contact 97 / 98 in position "Tripped": 8g / 11 ms
vibration resistance1 … 6 Hz, 15 mm; 6 … 500 Hz, 20 m/s²; 10 cycles
thermal current50 A
with automatic reset typical3 min
with remote-reset0 min
with manual reset0 min
reference code according to IEC 81346-2F
Substance Prohibitance (day/month/year)03/01/2017
SVHC substance nameLead CAS-No. 7439-92-1 Lead monoxide (lead oxide) CAS-No. 1317-36-8 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one CAS-No. 71868-10-5 Melamine CAS-No. 108-78-1 6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol CAS-No. 119-47-1
Net Weight527.38 g
Ambient conditions
installation altitude at height above sea level maximum2 000 m
during operation-25 ... +60 °C
during storage-40 ... +80 °C
during transport-40 ... +80 °C
temperature compensation-25 ... +60 °C
relative humidity during operation10 ... 95 %
Main circuit
number of poles for main current circuit3
adjustable current response value current of the current-dependent overload release12.5 ... 50 A
rated value1 000 V
at AC-3e rated value maximum1 000 V
operating frequency rated value50 ... 60 Hz
operational current rated value50 A
operational current at AC-3e at 400 V rated value50 A
for 3-phase motors at 400 V at 50 Hz7.5 ... 22 kW
for AC motors at 500 V at 50 Hz11 ... 30 kW
for AC motors at 690 V at 50 Hz11 ... 45 kW
Auxiliary circuit
design of the auxiliary switchintegrated
number of NC contacts for auxiliary contacts1
notefor contactor disconnection
number of NO contacts for auxiliary contacts1
notefor message "tripped"
number of CO contacts for auxiliary contacts0
at 24 V4 A
at 110 V4 A
at 120 V4 A
at 125 V4 A
at 230 V3 A
at 24 V2 A
at 60 V0.55 A
at 110 V0.3 A
at 125 V0.3 A
at 220 V0.11 A
Protective and monitoring functions
trip classCLASS 20E
design of the overload releaseelectronic
UL/CSA ratings
at 480 V rated value50 A
at 600 V rated value50 A
contact rating of auxiliary contacts according to ULB600 / R300
Short-circuit protection
— with type of coordination 1 requiredgG: 200 A
— with type of coordination 2 requiredgG: 200 A
for short-circuit protection of the auxiliary switch requiredfuse gG: 6 A
Installation/ mounting/ dimensions
mounting positionany
fastening methodContactor mounting
height106 mm
width70 mm
depth124 mm
— forwards0 mm
— backwards0 mm
— upwards0 mm
— at the side6 mm
— downwards0 mm
— forwards0 mm
— backwards0 mm
— upwards0 mm
— downwards0 mm
— at the side6 mm
Connections/ Terminals
product component removable terminal for auxiliary and control circuitYes
for main current circuitscrew-type terminals
for auxiliary and control circuitscrew-type terminals
arrangement of electrical connectors for main current circuitTop and bottom
solid2x (2.5 ... 16 mm²)
stranded2x 16 mm²
solid or stranded1x (2,5 ... 70 mm²), 2x (2,5 ... 50 mm²)
finely stranded with core end processing1x (2,5 ... 50 mm²), 2x (2,5 ... 35 mm²)
— solid1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
— solid or stranded1x (0,5 ... 4 mm²), 2x (0,5 ... 2,5 mm²)
— finely stranded with core end processing1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
for AWG cables for auxiliary contacts2x (20 ... 14)
for main contacts with screw-type terminals4.5 ... 6 N·m
for auxiliary contacts with screw-type terminals0.8 ... 1.2 N·m
design of screwdriver shaftDiameter 5 to 6 mm
size of the screwdriver tipPozidriv PZ 2
for main contactsM6
of the auxiliary and control contactsM3
Electrical Safety
protection class IP on the front according to IEC 60529IP20
touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front
Communication/ Protocol
type of voltage supply via input/output link masterNo
Electromagnetic compatibility
due to burst according to IEC 61000-4-42 kV (power ports), 1 kV (signal ports) corresponds to degree of severity 3
due to conductor-earth surge according to IEC 61000-4-52 kV (line to earth) corresponds to degree of severity 3
due to conductor-conductor surge according to IEC 61000-4-51 kV (line to line) corresponds to degree of severity 3
due to high-frequency radiation according to IEC 61000-4-610 V in frequency range 0.15 to 80 MHz, modulation 80 % AM with 1 kHz
field-based interference according to IEC 61000-4-310 V/m
electrostatic discharge according to IEC 61000-4-26 kV contact discharge / 8 kV air discharge
Display
display version for switching statusSlide switch