product brand nameSIRIUS
product designationcompact starter
design of the productreversing starter
product type designation3RA62
General technical data
product function control circuit interface to parallel wiringYes
product extension auxiliary switchYes
at AC in hot operating state0.01 W
at AC in hot operating state per pole0.01 W
without load current share typical6 W
insulation voltage rated value690 V
degree of pollution3
surge voltage resistance rated value6 000 V
between main and auxiliary circuit400 V
between auxiliary and auxiliary circuit250 V
between control and auxiliary circuit300 V
degree of protection NEMA ratingother
shock resistancea=60 m/s2 (6g) with 10 ms per 3 shocks in all axes
vibration resistancef = 4 ... 5.8 Hz, d = 15 mm; f = 5.8 ... 500 Hz, a = 20 m/s²; 10 cycles
of the main contacts typical10 000 000
of auxiliary contacts typical10 000 000
of the signaling contacts typical10 000 000
at DC-13 at 6 A at 24 V typical30 000
at AC-15 at 6 A at 230 V typical200 000
type of coordinationcontinous operation according to IEC 60947-6-2
reference code according to IEC 81346-2Q
Substance Prohibitance (day/month/year)05/01/2012
SVHC substance nameLead CAS-No. 7439-92-1 Lead monoxide (lead oxide) CAS-No. 1317-36-8 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one CAS-No. 71868-10-5 Melamine CAS-No. 108-78-1 6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol CAS-No. 119-47-1
Net Weight2.406 kg
Ambient conditions
installation altitude at height above sea level maximum2 000 m
during operation-20 ... +60 °C
during storage-55 ... +80 °C
during transport-55 ... +80 °C
relative humidity during operation10 ... 90 %
Main circuit
number of poles for main current circuit3
adjustable current response value current of the current-dependent overload release0.1 ... 0.4 A
formula for making capacity limit current120 x Ie
formula for limit current breaking capacity100 x Ie
at 400 V rated value0.09 kW
at 500 V rated value0.12 kW
at 690 V rated value0.18 kW
operating voltage at AC-3 rated value maximum690 V
at AC at 400 V rated value0.4 A
at AC-3 at 400 V rated value0.4 A
— at 400 V rated value0.3 A
— at 500 V rated value0.32 A
— at 690 V rated value0.35 A
at AC-3 at 400 V rated value0.09 kW
— at 400 V rated value90 W
— at 500 V rated value120 W
— at 690 V rated value180 W
no-load switching frequency3 600 1/h
at AC-41 according to IEC 60947-6-2 maximum750 1/h
at AC-43 according to IEC 60947-6-2 maximum250 1/h
Control circuit/ Control
type of voltageAC/DC
at 50 Hz rated value240 V
at 50 Hz110 ... 240 V
at 60 Hz110 ... 240 V
1 rated value50 Hz
2 rated value60 Hz
control supply voltage 1 at DC rated value240 V
control supply voltage 1 at DC110 ... 240 V
at AC maximum6 W
at DC maximum5.1 W
Auxiliary circuit
number of NC contacts for auxiliary contacts0
number of NO contacts for auxiliary contacts2
number of NO contacts of instantaneous short-circuit trip unit for signaling contact1
number of CO contacts of the current-dependent overload release for signaling contact1
operational current of auxiliary contacts at AC-12 maximum10 A
operational current of auxiliary contacts at DC-13 at 250 V0.27 A
Protective and monitoring functions
trip classCLASS 10 and 20 adjustable
at 400 V rated value53 kA
at 500 V rated value3 kA
at 690 V rated value3 kA
UL/CSA ratings
at 480 V rated value0.4 A
at 600 V rated value0.4 A
contact rating of auxiliary contacts according to ULcontacts 21-22, 13-14, 43-44 Q600 / A600, contacts 77-78 R300 / B300, contacts 95-96-98 R300 / D300
Short-circuit protection
product function short circuit protectionYes
design of short-circuit protectionelectromagnetic
for short-circuit protection of the auxiliary switch requiredfuse gL/gG: 10 A
for short-circuit protection of the signaling switch of the short-circuit release required6A gL/gG/400V
for short-circuit protection of the signaling switch of the overload release required4A gL/gG/400V
Installation/ mounting/ dimensions
mounting positionany
mounting position recommendedvertical, on horizontal standard DIN rail
fastening methodscrew and snap-on mounting
height191 mm
width90 mm
depth165 mm
Connections/ Terminals
product component removable terminal for main circuitYes
product component removable terminal for auxiliary and control circuitYes
for main current circuitspring-loaded terminals
for auxiliary and control circuitspring-loaded terminals
solid2x (1.5 ... 6 mm²), 1x 10 mm²
finely stranded with core end processing2x (1.5 ... 6 mm²)
finely stranded without core end processing2x (1.5 ... 6 mm²)
— solid2x (0.25 ... 1.5 mm²)
— finely stranded with core end processing2x (0.25 ... 1.5 mm²)
— finely stranded without core end processing2x (0.25 ... 1.5 mm²)
for AWG cables for auxiliary contacts2x (24 ... 16)
Safety related data
with low demand rate according to SN 3192040 %
with high demand rate according to SN 3192050 %
B10 value with high demand rate according to SN 319203 000 000
failure rate [FIT] with low demand rate according to SN 31920100 FIT
IEC 61508
T1 value for proof test interval or service life according to IEC 6150820 a
Electrical Safety
protection class IP on the front according to IEC 60529IP20
touch protection on the front according to IEC 60529finger-safe
Communication/ Protocol
product function bus communicationNo
AS-Interface protocolNo
IO-Link protocolNo
product function control circuit interface with IO linkNo
Electromagnetic compatibility
due to burst according to IEC 61000-4-44 kV main contacts, 2 kV auxiliary contacts
due to conductor-earth surge according to IEC 61000-4-54 kV main contacts, 2 kV auxiliary contacts
due to conductor-conductor surge according to IEC 61000-4-52 kV main contacts, 1 kV auxiliary contacts
due to high-frequency radiation according to IEC 61000-4-60.15-80Mhz at 10V
field-based interference according to IEC 61000-4-310 V/m
electrostatic discharge according to IEC 61000-4-28 kV
conducted HF interference emissions according to CISPR11150 kHz ... 30 MHz Class A
field-bound HF interference emission according to CISPR1130 ... 1000 MHz Class A
Supply voltage
Supply voltage required Auxiliary voltageNo
Display
number of LEDs3